Mich. Admin. Code R. 29.7038

Current through Vol. 24-24, January 15, 2025
Section R. 29.7038 - Outdoor locations

Rule 38. Sections 4-1, 4-1.1, and 4-1.2 were reproduced from NFPA 50A as follows:

4-1 Outdoor Locations.

4-1.1 Where protective walls or roofs are provided, they shall be constructed of noncombustible or limited-combustible materials.

4-1.2 Electrical equipment within 15 feet (4.6 m) shall be in accordance with Article 501 of NFPA 70, National Electrical Code, for Class I, Division 2 locations.

Mich. Admin. Code R. 29.7038

2008 AACS