Rule 20. Section 2-1.3 is reproduced from NFPA 50A, and sections 2-1, 2-1.1, 2-1.2, and 2-1.4 to 2-1.8.2 of the storage and handling of gaseous and Liquefied H2 code are added as follows:
2-1 Containers.
2-1.1 H2 containers shall comply with 1 of the following:
VIII, "Rules for the construction of pressure vessels, " adopted by reference in section 8-1.
2-1.2 Permanently installed aboveground containers shall be provided with substantial supports, constructed of noncombustible material on firm foundations of noncombustible material, and shall comply with the following subsections as applicable:
Exception: Supports may be greater than 18 inches (45.72 centimeters) if owner demonstrates, to the satisfaction of the department, that the container will not be exposed to a 2-hour pool fire.
Exception: Composite containers shall not be painted without prior permission from the container manufacturer.
Figure 2-1 .2______
2-1.3 Each portable container shall be legibly marked with the name hydrogen in accordance with ANSI/CGA C-4, Method of Marking Portable Compressed Gas Containers to Identify the Material Contained. Each manifold hydrogen supply unit shall be legibly marked with the name hydrogen or a legend such as "This unit contains hydrogen."
2-1.4 An owner or operator that has had a container subjected to heat exposure due to fire shall remove the container from service, unless the owner or operator provides documentation of recertification in accordance with section 2-1.1, to the department substantiating container integrity.
2-1.5 Guard posts or other approved means shall be provided to protect a container system subject to vehicular damage. When guard posts are installed, all of the following design specifications shall be met:
2-1.6 Physical protection. Containers, piping, valves, pressure-relief devices, regulating equipment, and other appurtenances shall be protected against physical damage and tampering.
2-1.7 Portable containers subject to shifting or upset shall be secured. Nesting may be used to secure portable containers.
2-1.8 Underground containers. Underground containers for the storage of gaseous H2 shall be in accordance with this subsection.
2-1.8.1 Construction. Storage containers for gaseous H2 shall be designed and constructed in accordance with Section VIII of ASME International, "Boiler and Pressure Vessel Code," adopted by reference in section 8-1, and shall be vacuum-jacketed in accordance with section 2-1.10.1.1.
2-1.8.2 Corrosion Protection. The underground container shall be protected by an engineered corrosion protection system designed by a corrosion expert. If cathodic protection is used the maintenance schedule shall meet the requirements of section 5-4.
Mich. Admin. Code R. 29.7020