Section R. 29.1842 - Life safety code; new nursing homes; adoption by referenceRule 42.
(1) The provisions of chapters 1 to 10, 11, 18, and 43 of the code that apply to new nursing home occupancies are adopted by reference in R 19.1802.(2) Section 18.4.3.7.2.1 is amended to read as follows: 18.4.3.7.2.1 Where the smoke compartment being modified is not protected throughout by an approved, supervised automatic sprinkler system in accordance with 19.3.5.7, all of the following shall apply:(1) Doors protecting corridor openings shall be constructed of 1-3/4 in. (44 mm) thick, solid-bonded core wood or of construction that resists the passage of fire for a minimum of 20 minutes.(2) Door frames shall be labeled or of steel construction.Mich. Admin. Code R. 29.1842