Mich. Admin. Code R. 408.7101

Current through Vol. 24-24, January 15, 2025
Section R. 408.7101 - Wiring and lighting

Rule 101.

(1) Electric wiring shall be in rigid metal conduit or electrical metallic tubing.
(2) A traveling cable used between the car and hoistway wiring shall be in compliance with the Michigan electrical code.
(3) A fused disconnect main line switch externally operated shall be provided adjacent to the controller.
(4) Hoistway lighting shall be provided.

Mich. Admin. Code R. 408.7101

2003 AACS