Section R. 408.7079 - Rated load safety testRule 79. Section 26.4.8 of the ANSI A10.4 standard is amended to read as follows:
26.4.8 A rated load safety test, as required by section 26.2.1.1 of the ANSI A10.4 standard, must be performed by a licensed elevator contractor in the presence of a general elevator inspector every 90 days. Periodic inspections may be conducted every 30 days and the appropriate fees assessed at the discretion of the department.Mich. Admin. Code R. 408.7079