Mich. Admin. Code R. 408.7054

Current through Vol. 24-24, January 15, 2025
Section R. 408.7054 - Skirt deflector devices

Rule 54. Section 6.1.3.3.10 of the ASME A17.1 code is amended to read as follows:

6.1.3.3.10 Deflector devices are permitted. Where provided, deflector devices must extend from skirt panels parallel to the escalator path of travel. Means to secure these deflector devices may be on the exposed surface of the skirt. All fasteners must be of steel with machine screw threads. Any exposed fastener heads shall be of the tamper-resistant type and flush to within 1 mm, or 0.04 inch
(1) Rigid elements must comply with the following conditions:
(a) Horizontal protrusions extending above the step must be 18 mm, or 0.75 inch maximum. Corners or changes in profile must be rounded or beveled.

The exposed surfaces of such elements must be smooth and permanently treated with a low-friction material.

(b) On the incline, the area of any protrusion must lie entirely offset outward from a line beginning on the vertical portion of the skirt panel measured 25 mm, or 1 inch vertically above the step nose line. The lower surface must be beveled not less than 10 degrees upward and the upper surface must be beveled not less than 15 degrees downward in compliance with Figure 6.1.3.3.10 of the ASME A17.1 code.
(c) At the upper and lower landing, any protrusion must lie entirely above a line beginning on the vertical portion of the skirt panel 50 mm, or 2 inches, above the step nose line. The lower surface must be beveled not less than 10 degrees upward and the upper surface must be beveled not less than 15 degrees downward. Any rigid elements at the landings must smoothly blend into the rigid elements along the incline in accordance with the radius of curvature of the transition zone.
(d) If attached to the skirt, rigid elements must withstand a force of 900 N (200 lbf) perpendicular to the line of attachment of the element without detachment or permanent deformation. The force shall be applied to an area of 645 mm' (1 inch').
(2) Flexible elements must comply with the following conditions:
(a) The horizontal protrusion extending from the skirt surface above the step must be 50 mm, or 2 inches, maximum.
(b) Must be capable of deflecting to an angle of 10 degrees or greater above the horizontal protrusion.
(c) Noncontinuous flexible elements are allowed to deflect to allow a maximum of 9.5 mm, or 0.375 inch interference with any point on the step surface.
(d) Continuous flexible elements may not deflect such that they can contact the steps.

Mich. Admin. Code R. 408.7054