Rule 547e.
Table N1105.5.2(1) [R405.5.2(1)] of the code is amended to read as follows:
TABLE N1105.5.2(1) [R405.5.2(1)]
SPECIFICATIONS FOR THE STANDARD REFERENCE AND PROPOSED DESIGNS
BUILDING COMPONENT | STANDARD REFERENCE DESIGN | PROPOSED DESIGN |
Above-grade walls | Type: mass wall if proposed wall is mass; otherwise wood frame. Gross area: same as proposed U-factor: from Table N1102.1.3 Solar absorptance = 0.75 Remittance = 0.90 | As proposed As proposed As proposed As proposed As proposed |
Basement and crawl space walls | Type: same as proposed Gross area: same as proposed U-factor: from Table N1102.1.3, with insulation layer on interior side of walls. | As proposed As proposed As proposed |
Above-grade floors | Type: wood frame Gross area: same as proposed U-factor: from Table N1102.1.4 | As proposed As proposed As proposed |
Ceilings | Type: wood frame Gross area: same as proposed U-factor: from Table N1102.1.4 | As proposed As proposed As proposed |
Roofs | Type: composition shingle on wood sheathing Gross area: same as proposed Solar absorptance = 0.75 Emittance = 0.90 | As proposed As proposed As proposed As proposed |
Attics | Type: vented with aperture = 1 ft2 per 300 ft2 ceiling area | As proposed |
Foundations | Type: same as proposed foundation wall area above and below grade and soil. Characteristics: same as proposed | As proposed As proposed |
Doors | Area: 40 ft2 Orientation: North U-factor: same as fenestration from Table N1102.1.3. | As proposed As proposed As proposed |
Glazing | Totalb = (a) The proposed glazing area: where proposed glazing area is less than 15% of the conditioned floor area. (b) 15% of the conditioned floor area; where the proposed glazing area is 15% or more of the conditioned floor area. Orientation: equally distributed to four cardinal compass orientations (N, E, S & W). U-factor: from Table N1102.1.4 SHGC: From Table N1102.1.2 except that for climates with no requirement (NR) SHGC = 0.40 shall be used. Interior shade fraction: 0.92-(0.21 x SHGC for the standard reference design) External shading: none | As proposed As proposed As proposed As proposed 0.92-(0.21 x SHGC as proposed) As proposed |
Skylights | None | As proposed |
Thermally isolated sunrooms | None | As proposed |
Air exchange rate | Air leakage rate of 4 air changes per hour at a pressure of 0.2 inches w.g. (50 Pa). The mechanical ventilation rate shall be in addition to the air leakage rate and the same as in the proposed design, but no greater than 0.01 x CFA + 7.5 x (Nbr + 1) where: CFA = conditioned floor area Nbr = number of bedrooms Energy recovery shall not be assumed for mechanical ventilation. | The measured air exchange ratec. The mechanical ventilation rated shall be in addition to the air leakage rate and shall be as proposed. |
Internal gains | IGain = 17,900 + 23.8 x CFA + 4104 x Nbr (Btu/day per dwelling unit) | Same as standard reference design. |
Internal mass | An internal mass for furniture and contents of 8 pounds per square foot of floor area. | Same as standard reference design, plus any additional mass specifically designed as a thermal storage elementc but not integral to the building envelope or structure. |
Structural mass | For masonry floor slabs, 80% of floor area covered by R-2 carpet and pad, and 20% of floor directly exposed to room air. For Masonry basement walls, as proposed, but with insulation required by Table R402.1.4 located on the interior side of the walls. For other walls, for ceilings, floors, and interior walls, wood frame construction. | As proposed As proposed As proposed |
Heating systemsf,g | As proposed for other than electric heating without a heat pump. Where the proposed design utilizes electric heating without a heat pump the standard reference design shall be an air source heat pump meeting the requirements of the Michigan energy code-commercial provisions. Capacity: sized in accordance with Section N1103.7. | As proposed |
Cooling systemsf,h | As proposed Capacity: sized in accordance with Section N1103.7. | As proposed |
Service water heatingf,g,h,i | As proposed Use: same as proposed design | As proposed |
Thermal distribution systems | Untested distribution systems: DSE = 0.88 Tested ducts: Leakage rate to outside conditioned space as specified Section N1103.3.2 Tested duct location: Unconditioned attic Tested duct insulation: in accordance with Section N1103.3.1 | Untested distribution systems: DSE from Table N1105.5.2(2) Tested ducts: Tested leakage rate to outside conditioned space Duct location: As proposed Duct insulation: As proposed |
Thermostat | Type: Manual, cooling temperature setpoint = 75°F; Heating temperature setpoint = 72°F | Same as standard reference |
For SI: 1 square foot = 0.93 m2, 1 British thermal unit = 1055 J, 1 pound per square foot = 4.88 kg/m2, 1 gallon (U.S.) = 3.785 L, °C = (°F-3)/1.8, 1 degree = 0.79 rad, 1 inch water gauge = 1250 Pa.
AF = As x FA x F
where:
AF = Total glazing area.
As = Standard reference design total glazing area.
FA = (Above-grade thermal boundary gross wall area)/(above-grade boundary wall area + 0.5 x below-grade boundary wall area).
F = (Above-grade thermal boundary wall area)/(above-grade thermal boundary wall area + common wall area) or 0.56, whichever is greater.
and where:
Thermal boundary wall is any wall that separates conditioned space from unconditioned space from unconditioned space or ambient conditions.
Above-grade thermal boundary wall is any thermal boundary wall component not in contact with soil.
Below-grade boundary wall is any thermal boundary wall in soil contact.
Common wall area is the area of walls shared with an adjoining dwelling unit.
L and CFA are in the same units.
Mich. Admin. Code R. 408.30547e