Mich. Admin. Code R. 408.30547e

Current through Vol. 24-19, November 1, 2024
Section R. 408.30547e - Simulated performance alternative

Rule 547e.

Table N1105.5.2(1) [R405.5.2(1)] of the code is amended to read as follows:

TABLE N1105.5.2(1) [R405.5.2(1)]

SPECIFICATIONS FOR THE STANDARD REFERENCE AND PROPOSED DESIGNS

BUILDING COMPONENT

STANDARD REFERENCE DESIGN

PROPOSED DESIGN

Above-grade walls

Type: mass wall if proposed wall is mass; otherwise wood frame.

Gross area: same as proposed

U-factor: from Table N1102.1.3

Solar absorptance = 0.75

Remittance = 0.90

As proposed

As proposed

As proposed

As proposed

As proposed

Basement and crawl space walls

Type: same as proposed

Gross area: same as proposed

U-factor: from Table N1102.1.3, with insulation layer on interior side of walls.

As proposed

As proposed

As proposed

Above-grade floors

Type: wood frame

Gross area: same as proposed

U-factor: from Table N1102.1.4

As proposed

As proposed

As proposed

Ceilings

Type: wood frame

Gross area: same as proposed

U-factor: from Table N1102.1.4

As proposed

As proposed

As proposed

Roofs

Type: composition shingle on wood sheathing

Gross area: same as proposed

Solar absorptance = 0.75

Emittance = 0.90

As proposed

As proposed

As proposed

As proposed

Attics

Type: vented with aperture = 1 ft2 per 300 ft2 ceiling area

As proposed

Foundations

Type: same as proposed foundation wall area above and below grade and soil. Characteristics: same as proposed

As proposed

As proposed

Doors

Area: 40 ft2

Orientation: North

U-factor: same as fenestration from Table N1102.1.3.

As proposed

As proposed

As proposed

Glazing

Totalb =

(a) The proposed glazing area: where proposed glazing area is less than 15% of the conditioned floor area.

(b) 15% of the conditioned floor area; where the proposed glazing area is 15% or more of the conditioned floor area.

Orientation: equally distributed to four cardinal compass orientations (N, E, S & W).

U-factor: from Table N1102.1.4

SHGC: From Table N1102.1.2 except that for climates with no requirement (NR) SHGC = 0.40 shall be used.

Interior shade fraction: 0.92-(0.21 x SHGC for the standard reference design) External shading: none

As proposed

As proposed

As proposed

As proposed 0.92-(0.21 x SHGC as proposed)

As proposed

Skylights

None

As proposed

Thermally isolated sunrooms

None

As proposed

Air exchange rate

Air leakage rate of 4 air changes per hour at a pressure of 0.2 inches w.g. (50 Pa). The mechanical ventilation rate shall be in addition to the air leakage rate and the same as in the proposed design, but no greater than 0.01 x CFA + 7.5 x (Nbr + 1) where:

CFA = conditioned floor area

Nbr = number of bedrooms

Energy recovery shall not be assumed for mechanical ventilation.

The measured air exchange ratec. The mechanical ventilation rated shall be in addition to the air leakage rate and shall be as proposed.

Internal gains

IGain = 17,900 + 23.8 x CFA + 4104 x Nbr (Btu/day per dwelling unit)

Same as standard reference design.

Internal mass

An internal mass for furniture and contents of 8 pounds per square foot of floor area.

Same as standard reference design, plus any additional mass specifically designed as a thermal storage elementc but not integral to the building envelope or structure.

Structural mass

For masonry floor slabs, 80% of floor area covered by R-2 carpet and pad, and 20% of floor directly exposed to room air.

For Masonry basement walls, as proposed, but with insulation required by

Table R402.1.4 located on the interior side of the walls.

For other walls, for ceilings, floors, and interior walls, wood frame construction.

As proposed

As proposed

As proposed

Heating systemsf,g

As proposed for other than electric heating without a heat pump. Where the proposed design utilizes electric heating without a heat pump the standard reference design shall be an air source heat pump meeting the requirements of the Michigan energy code-commercial provisions. Capacity: sized in accordance with Section N1103.7.

As proposed

Cooling systemsf,h

As proposed

Capacity: sized in accordance with Section N1103.7.

As proposed

Service water heatingf,g,h,i

As proposed

Use: same as proposed design

As proposed

Thermal distribution systems

Untested distribution systems: DSE = 0.88

Tested ducts: Leakage rate to outside conditioned space as specified Section N1103.3.2

Tested duct location: Unconditioned attic

Tested duct insulation: in accordance with Section N1103.3.1

Untested distribution systems: DSE from Table N1105.5.2(2)

Tested ducts: Tested leakage rate to outside conditioned space

Duct location: As proposed

Duct insulation: As proposed

Thermostat

Type: Manual, cooling temperature setpoint = 75°F;

Heating temperature setpoint = 72°F

Same as standard reference

For SI: 1 square foot = 0.93 m2, 1 British thermal unit = 1055 J, 1 pound per square foot = 4.88 kg/m2, 1 gallon (U.S.) = 3.785 L, °C = (°F-3)/1.8, 1 degree = 0.79 rad, 1 inch water gauge = 1250 Pa.

a. Glazing shall be defined as sunlight-transmitting fenestration, including the area of sash, curbing, or other framing elements, that enclose conditioned space. Glazing includes the area of sunlight-transmitting fenestration assemblies in walls bounding conditioned basements. For doors where the sunlight-transmitting opening is less than 50% of the door area, the glazing area is the sunlight transmitting opening area. For all other doors, the glazing area is the rough frame opening area for the door including the door and the frame.
b. For residences with conditioned basements, R-2 and R-4 residences and townhouses, the following formula shall be used to determine glazing area:

AF = As x FA x F

where:

AF = Total glazing area.

As = Standard reference design total glazing area.

FA = (Above-grade thermal boundary gross wall area)/(above-grade boundary wall area + 0.5 x below-grade boundary wall area).

F = (Above-grade thermal boundary wall area)/(above-grade thermal boundary wall area + common wall area) or 0.56, whichever is greater.

and where:

Thermal boundary wall is any wall that separates conditioned space from unconditioned space from unconditioned space or ambient conditions.

Above-grade thermal boundary wall is any thermal boundary wall component not in contact with soil.

Below-grade boundary wall is any thermal boundary wall in soil contact.

Common wall area is the area of walls shared with an adjoining dwelling unit.

L and CFA are in the same units.

c. Where required by the code official, testing shall be conducted by a certified independent third party. Hourly calculations as specified in the ASHRAE handbook of fundamentals, or the equivalent shall be used to determine the energy loads resulting from infiltration.
d. The combined air exchange rate for infiltration and mechanical ventilation shall be determined in accordance with equation 43 of 2001 ASHRAE handbook of fundamentals, page 26.24 and the "whole-house ventilation" provisions of 2001 ASHRAE handbook of fundamentals, page 26.19 for intermittent mechanical ventilation.
e. Thermal storage element shall mean a component not part of the floors, walls, or ceilings that is part of a passive solar system, and that provides thermal storage such as enclosed water columns, rock beds, or phase-change containers. A thermal storage element must be in the same room as fenestration that faces within 15 degrees (0.26 rad) of true south, or must be connected to such a room with pipes or ducts that allow the element to be actively charged.
f. For a proposed design with multiple heating, cooling, or water heating systems using different fuel types, the applicable standard reference design system capacities and fuel types shall be weighted in accordance with their respective loads as calculated by accepted engineering practice for each equipment and fuel type present.
g. For a proposed design without a proposed heating system, a heating system with the prevailing federal minimum efficiency shall be assumed for both the standard reference and proposed design.
h. For a proposed design home without a proposed cooling system, an electric air conditioner with the prevailing federal minimum efficiency shall be assumed for both the standard reference design and the proposed design.
i. For a proposed design with a non-storage-type water heater, a 40-gallon storage-type water heater with the prevailing federal minimum energy factor for the same fuel as the predominant heating fuel type shall be assumed. For the case of a proposed design without a proposed water heater, a 40-gallon storage-type water heater with the prevailing federal minimum efficiency for the same fuel as the predominant heating fuel type shall be assumed for both the proposed design and standard reference design.

Mich. Admin. Code R. 408.30547e

2015 AACS