Rule 544b.
Section R302.5.1 of the code is amended and table R302.1(1) is added to read as follows:
TABLE R302.1(1)
EXTERIOR WALLS
EXTERIOR WALL ELEMENT | MINIMUM FIRE-RESISTANCE RATING | MINIMUM FIRE SEPARATION DISTANCE | |
Walls | Fire-resistance rated | 1 hour-tested in accordance with ASTM E 119 or UL 263 with exposure from both sides | [LESS THAN] 5 feet |
Not fire-resistance rated | 0 hours | [GREATER THAN EQUAL TO] 5 feet | |
Projections | Not alloweda | NA | [LESS THAN] 2 feet |
Fire-resistance rated | 1 hour on the underside | [GREATER THAN EQUAL TO] 2 feet to [LESS THAN] 5 feet | |
Not fire-resistance rated | 0 hours | [GREATER THAN EQUAL TO] 5 feet | |
Opening in walls | Not allowed | N/A | [LESS THAN] 3 feet |
25% maximum of wall area | 0 hours | 3 feet | |
Unlimited | 0 hours | 5 feet | |
Penetrations | All | Comply with Section R302.4 | [LESS THAN] 5 feet |
None required | 5 feet |
For SI: 1 foot = 304.8 mm
N/A = Not applicable
Mich. Admin. Code R. 408.30544b