Mich. Admin. Code R. 408.30544b

Current through Vol. 24-10, June 15, 2024
Section R. 408.30544b - Exterior walls

Rule 544b.

Section R302.5.1 of the code is amended and table R302.1(1) is added to read as follows:

R302.5.1. Opening protection. Openings from a private garage directly into a room used for sleeping purposes shall not be permitted. Other openings between the garage and residence shall be equipped with solid wood doors not less than 1 3/8 inches (35 mm) in thickness, solid or honeycomb-core steel doors not less than 1 3/8 inches (35 mm) thick, or 20-minute fire-rated doors.

TABLE R302.1(1)

EXTERIOR WALLS

EXTERIOR WALL ELEMENT

MINIMUM FIRE-RESISTANCE RATING

MINIMUM FIRE

SEPARATION

DISTANCE

Walls

Fire-resistance rated

1 hour-tested in accordance with ASTM E 119 or UL 263 with exposure from both sides

[LESS THAN] 5 feet

Not fire-resistance rated

0 hours

[GREATER THAN EQUAL TO] 5 feet

Projections

Not alloweda

NA

[LESS THAN] 2 feet

Fire-resistance rated

1 hour on the underside

[GREATER THAN EQUAL TO] 2 feet to [LESS THAN] 5 feet

Not fire-resistance rated

0 hours

[GREATER THAN EQUAL TO] 5 feet

Opening in walls

Not allowed

N/A

[LESS THAN] 3 feet

25% maximum of wall area

0 hours

3 feet

Unlimited

0 hours

5 feet

Penetrations

All

Comply with Section R302.4

[LESS THAN] 5 feet

None required

5 feet

For SI: 1 foot = 304.8 mm

N/A = Not applicable

a. except as allowed as per Section R302.1 exceptions 3 and 4

Mich. Admin. Code R. 408.30544b

MR 19, Eff. 2/6/2016