Current through Vol. 24-19, November 1, 2024
Section R. 408.30532 - Roof extensionRule 532. Section P3103.1 of the code is amended to read as follows:
P3103.1. Roof extension. All open vent pipes that extend through a roof shall terminate at least 1 foot (305 mm) above the roof, except that if a roof is to be used for any purpose other than weather protection, then the vent extension shall be run not less than 7 feet (2134 mm) above the roof.Mich. Admin. Code R. 408.30532