Mich. Admin. Code R. 408.30525a

Current through Vol. 24-19, November 1, 2024
Section R. 408.30525a - Simplified wall bracing

Rule 525a.

Section R 602.10.9 is amended to read as follows:

R602.10.9. Braced wall panel support. Braced wall panel support shall be provided as follows:
1. Cantilevered floor joists complying with section R502.3.3 shall be permitted to support braced wall panels.
2. Raised floor system post or pier foundations supporting braced wall panels shall be designed in accordance with accepted engineering practice.
3. Masonry stem walls with a length of 48 inches (1 219 mm) or less supporting braced wall panels shall be reinforced in accordance with figure R602.10.9. Masonry stem walls with a length greater than 48 inches (1 219 mm) supporting braced wall panels shall be constructed in accordance with section R403.1. Methods ABW and PFH shall not be permitted to attach to masonry stem walls.
4. Concrete stem walls with a length of 48 inches (1 219 mm) or less, greater than 12 inches (305 mm) tall shall have reinforcement sized and located in accordance with figure R602.10.9.

Mich. Admin. Code R. 408.30525a

MR 19, Eff. 2/6/2016