Mich. Admin. Code R. 408.30443

Current through Vol. 24-19, November 1, 2024
Section R. 408.30443 - Masonry

Rule 443. Section 1405.4.2 of the code is amended to read as follows:

1405.4.2. Masonry. Flashing and weep holes shall be located in the first course of masonry above finished ground level above the foundation wall or slab; at the heads of windows, doors, and other wall openings; at window sills and at other points of support including structural floors, shelf angles, and lintels where anchored veneers are designed in accordance with section 1405.6. Flashing shall extend to, or beyond, the finished face of the wall.