Section R. 408.31098b - (C506.3) System commissioningR1098a. Section 6.7.2.4 of the standard is amended to read as follows:
6.7.2.4. System Commissioning. HVAC control systems shall be tested to ensure that control elements are calibrated, adjusted, and in proper working condition. For projects larger than 10,000 ft2, conditioned area, except warehouses and semiheated spaces, detailed instructions for commissioning HVAC systems (see informative appendix E) shall be provided by the designer in plans and specifications.Mich. Admin. Code R. 408.31098b