Rule 321.
TABLE 2
Location of Nurse Call Devices
Key: * Required
[] Optional, but must be justified
Area Designation | Patient Station | Patient Bath Station | Emergency Signal Station | Code Call Station | Nurse Master Station | Duty Station | Notes |
Nursing Units | |||||||
Inpatient Bed Location | * | * | [] | ||||
Patient Water Closets, Showers, and Baths | * | ||||||
Nurse Control Station | * | ||||||
Clean Workroom | * | ||||||
Clean Supply Room | [] | ||||||
Soiled Workroom | * | ||||||
Soiled Holding Room | [] | ||||||
Medication Preparation Room | * | ||||||
Examination or Treatment Room | [] | * | * | ||||
Nurse Lounge | * | ||||||
Clean Linen Storage | [] | ||||||
Nourishment Station | [] | ||||||
Equipment Storage Room | [] | ||||||
Multi-Purpose Room | [] | ||||||
Other Clinical Areas | |||||||
Operating or Delivery Rooms | * | [] | |||||
Procedure Rooms | * | [] | |||||
Labor, Delivery, Recovery, Post-Partum Rooms | * | * | * | ||||
Recovery Phase 1 | [] | * | * | [] | |||
Recovery Phase 2 | * | * | [] | [] | |||
Emergency Exam, Treatment and Triage Areas | * | * | * | [] | 1,2,4 | ||
Patient Preparation and Holding Areas | * | * | [] | [] | 1,2 | ||
Critical Care Bed Locations, including NICU | * | * | * | [] | 1,2,3,4 | ||
Newborn and Special Care Nurseries | * | [] | |||||
Cardiac Catheterization, Interventional and Radiological Areas Angiography | [] | * | * | [] | |||
MRI, CT, Stress Testing Areas | [] | * | * | 2,4 | |||
Outpatient Examination Areas | [] | [] | |||||
Outpatient Waiting and Changing Areas | [] | 2 | |||||
Psychiatric Seclusion, Ante, and Exam Rooms | * | [] | |||||
Outpatient Toilet Rooms, Showers, Baths | [] | 2 | |||||
Psychiatric Patient 2 Room | [] | 2 | |||||
Notes: | |||||||
1. One device may accommodate both patient station and emergency staff assistance station functionality. | |||||||
2. Must activate a visible signal in the corridor at the patients door, at the nurse control station, and all duty stations. | |||||||
3. Provide 2-way voice communication with nurse control station. | |||||||
4. One device may accommodate both emergency staff assistance and code call station functionality. | |||||||
5. Patient station not required in NICU. |
Mich. Admin. Code R. 325.45321