(1) A nurse call system must be provided in each facility. This system must provide call devices of the designated types shown at the locations identified in Table 2.
(2) A health facility shall provide a telephone service that is available on patient care units.

TABLE 2

Location of Nurse Call Devices

Key: * Required

[] Optional, but must be justified

Area Designation

Patient Station

Patient Bath Station

Emergency Signal Station

Code Call Station

Nurse Master Station

Duty Station

Notes

Nursing Units

Inpatient Bed Location

*

*

[]

Patient Water Closets, Showers, and Baths

*

Nurse Control Station

*

Clean Workroom

*

Clean Supply Room

[]

Soiled Workroom

*

Soiled Holding Room

[]

Medication Preparation Room

*

Examination or Treatment Room

[]

*

*

Nurse Lounge

*

Clean Linen Storage

[]

Nourishment Station

[]

Equipment Storage Room

[]

Multi-Purpose Room

[]

Other Clinical Areas

Operating or Delivery Rooms

*

[]

Procedure Rooms

*

[]

Labor, Delivery, Recovery, Post-Partum Rooms

*

*

*

Recovery Phase 1

[]

*

*

[]

Recovery Phase 2

*

*

[]

[]

Emergency Exam, Treatment and Triage Areas

*

*

*

[]

1,2,4

Patient Preparation and Holding Areas

*

*

[]

[]

1,2

Critical Care Bed Locations, including NICU

*

*

*

[]

1,2,3,4

Newborn and Special Care Nurseries

*

[]

Cardiac

Catheterization, Interventional and Radiological Areas Angiography

[]

*

*

[]

MRI, CT, Stress Testing Areas

[]

*

*

2,4

Outpatient Examination Areas

[]

[]

Outpatient Waiting and Changing Areas

[]

2

Psychiatric Seclusion, Ante, and Exam Rooms

*

[]

Outpatient Toilet Rooms, Showers, Baths

[]

2

Psychiatric Patient 2

Room

[]

2

Notes:

1. One device may accommodate both patient station and emergency staff assistance station functionality.

2. Must activate a visible signal in the corridor at the patients door, at the nurse control station, and all duty stations.

3. Provide 2-way voice communication with nurse control station.

4. One device may accommodate both emergency staff assistance and code call station functionality.

5. Patient station not required in NICU.