Mich. Admin. Code R. 408.10671

Current through Vol. 24-13, August 1, 2024
Section R. 408.10671 - Fire escape stairs

Rule 671.

(1) Fire escape stairs may be used as a required exit only in existing buildings. Fire escape stairs shall not constitute more than 50% of the required exit capacity. Fire escape stairs shall not constitute any part of the required exits for a new building.
(2) Fire escape stair dimensions shall be in accordance with table 4.

TABLE 4
Minimum Width 22 inches clear between rails
Minimum horizontal dimension of a landing or platform 22 inches
Maximum rise 9 inches
Minimum tread, exclusive of nosing 9 inches
Spiral winders Not permitted
Maximum height between landings 12 feet

(3) Fire escape stairs shall have walls or approved guards, and handrails on both sides.

Mich. Admin. Code R. 408.10671

1979 AC; 2015 MR 8, Eff. April 29, 2015