Current through Vol. 24-19, November 1, 2024
Section R. 408.41855 - Fire hose and connectionsRule 1855.
(1) One-hundred feet or less of 1-1/2 inch hose, with a nozzle capable of discharging water at 25 gallons or more per minute supplied from an approved standpipe system may be substituted for a fire extinguisher rated not more than 2A in the designated area provided that the hose line can reach all points in the area.(2) The employer shall contact the local fire fighting organization to assure that fire hose connections on the jobsite are compatible with their fire fighting equipment. If a connection is not compatible, the employer shall install an adapter, or equivalent, to permit connection of local fire fighting equipment.(3) During demolition involving combustible materials, charged hose lines, supplied by hydrants, water tank trucks with pumps, or equivalent, shall be made available.Mich. Admin. Code R. 408.41855
1979 AC; 1983 AACS; 2015 MR 7, Eff. April 14, 2015