Rule 561.
If the shaft does not extend through the roof of the building, the top shall be covered with noncombustible material that affords at least a 1-hour resistance to fire. There shall be no openings into the shaft other than those necessary for the intended use of the laundry chute. Feed doors shall be located in an enclosed sprinklered room or compartment that is separated from other parts of the building by walls, a floor, and a ceiling which have a fire-resistance rating of not less than 1 hour.
Openings to such rooms or compartments shall be protected by B-labeled fire doors in labeled frames.
Mich. Admin. Code R. 400.10561