Mich. Admin. Code R. 325.10829

Current through Vol. 24-19, November 1, 2024
Section R. 325.10829 - Well appurtenances; type I public water supplies

Rule 829.

(1) The following is required of each well serving type I public water supplies:
(a) Each well shall be equipped with a meter or other acceptable means to measure the volume of water produced.
(b) Each well shall be provided with an electrical outlet energized with the pump motor, chemical injection taps, and space necessary for the addition of chemicals so that treatment equipment can be readily connected to the well discharge line in the event the department requires chemical treatment to protect the public health.
(c) Each well shall be equipped to allow pumping to waste without interrupting normal service in the distribution system.
(d) Each well shall be equipped with a means to measure the water level.
(2) Subdivisions (a) and (b) of subrule (1) do not apply to individual wells which are a part of a multiple well field serving a type I public water supply if the multiple well field is equipped in accordance with the provisions of subdivisions (a) and (b) or where a well is a raw water source for a treatment system when the treatment system is equipped with a meter or other acceptable means to measure the volume of water produced.

Mich. Admin. Code R. 325.10829

1979 AC