Rule 611b.
For a supply using... | (i) The turbidity level of representative samples of a supply's filtered water shall at no time exceed... | (ii) Not less than 95% of the measurements taken each month shall be less than or equal to... |
(a) Conventional, direct, or membrane filtration | 1 ntu | 0.3 ntu |
(b) Slow sand or diatomaceous earth filtration | 5 ntu | 1 ntu |
(c) An alternative filtration technology approved by the department, based on the demonstration described in subrule (3) of this rule. | The department-set turbidity level, not to exceed 5 ntu, based on the demonstration described in subrule (3) of this rule. | The department-set turbidity level, not to exceed 1 ntu, based on the demonstration described in subrule (3) of this rule. |
Mich. Admin. Code R. 325.10611b