Mich. Admin. Code R. 325.10610d

Current through Vol. 24-19, November 1, 2024
Section R. 325.10610d - Disinfection byproducts; requirements

Rule 610d.

(1) This rule and R 325.10719h to R 325.10719n establish monitoring and other requirements for achieving compliance with maximum contaminant levels based on locational running annual averages (LRAA) for total trihalomethanes (TTHM) and haloacetic acids (five) (HAA5), and for achieving compliance with maximum residual disinfectant residuals for chlorine and chloramine for certain consecutive supplies.
(2) Subject to these requirements are community and nontransient noncommunity water supplies that use a primary or residual disinfectant other than ultraviolet light or delivers water that has been treated with a primary or residual disinfectant other than ultraviolet light. These public water supplies are considered "water supplies" or "supplies" in this rule and R 325.10719h to R 325.10719n.
(3) The supply shall comply with all of the following provisions:
(a) The supply shall comply with the requirements in this rule and R 325.10719h to R325.10719n when the supply becomes subject to this rule as indicated in subrule (2) of this rule.
(b) The monitoring frequency is specified in R 325.10719h(1)(a) and both of the following:
(i) If the supply is required to conduct quarterly monitoring, the supply shall begin monitoring in the first full calendar quarter that the supply becomes subject to this rule, as indicated in subrule (2) of this rule.
(ii) If the supply is required to conduct monitoring at a frequency that is less than quarterly, the supply shall begin monitoring in the calendar month identified in the monitoring plan developed under R 325.10719i not later than 12 months after the supply becomes subject to this rule, as indicated in subrule (2) of this rule.
(c) If the supply is required to conduct quarterly monitoring, the supply shall make compliance calculations at the end of the fourth calendar quarter that follows the compliance date and at the end of each subsequent quarter (or earlier if the LRAA calculated based on fewer than 4 quarters of data would cause the MCL to be exceeded regardless of the monitoring results of subsequent quarters). If the supply is required to conduct monitoring at a frequency that is less than quarterly, the supply shall make compliance calculations beginning with the first compliance sample taken after the compliance date.
(d) For the purpose of the schedule in this subrule, the department may determine that the combined distribution system does not include certain consecutive supplies based on factors such as receiving water from a wholesale supply only on an emergency basis or receiving only a small percentage and small volume of water from a wholesale supply. The department may also determine that the combined distribution system does not include certain wholesale supplies based on factors such as delivering water to a consecutive supply only on an emergency basis or delivering only a small percentage and small volume of water to a consecutive supply.
(4) Compliance with the MCLs shall be based on both of the following:
(a) This subdivision applies to supplies required to monitor quarterly. To comply with MCLs in R 325.10610(2), the supply shall calculate LRAAs for TTHM and HAA5 using monitoring results collected under this rule and R 325.10719h to R 325.10719n and determine that each LRAA does not exceed the MCL. If the supply fails to complete 4 consecutive quarters of monitoring, the supply shall calculate compliance with the MCL based on the average of the available data from the most recent 4 quarters. If the supply takes more than 1 sample per quarter at a monitoring location, the supply shall average all samples taken in the quarter at that location to determine a quarterly average to be used in the LRAA calculation.
(b) This subdivision applies to supplies required to monitor annually or less frequently. To determine compliance with MCLs in R 325.10610(2), the supply shall determine that each sample taken is less than the MCL. If a sample exceeds the MCL, the supply shall comply with the requirements of R 325.10719k. If no sample exceeds the MCL, the sample result for each monitoring location is considered the LRAA for that monitoring location.
(5) The supply is in violation of the MCL when the LRAA exceeds the MCLs in R 325.10610(2), calculated based on 4 consecutive quarters of monitoring, or the LRAA calculated based on fewer than 4 quarters of data if the MCL would be exceeded regardless of the monitoring results of subsequent quarters. The supply is in violation of the monitoring requirements for each quarter that a monitoring result would be used in calculating an LRAA if the supply fails to monitor.
(6) A consecutive supply that does not add a disinfectant but delivers water that has been treated with a primary or residual disinfectant other than ultraviolet light, shall comply with monitoring requirements for chlorine and chloramines in R 325.10719e(3)(a) and the compliance requirements in R 325.10610b(1)(c) and (3)(a) and shall report monitoring results under R 325.10719f(3)(a).

Mich. Admin. Code R. 325.10610d

2003 AACS; 2009 AACS; 2015 MR 20, Eff. 10/16/2015