Mich. Admin. Code R. 325.11015

Current through Vol. 24-19, November 1, 2024
Section R. 325.11015 - Pumping facility; pressure

Rule 1015.

(1) All finished water pumping facilities shall be designed to maintain a minimum pressure of 5 psi gauge in all buried suction piping and suction piping subject to flooding.
(2) For finished water pumping facilities taking direct suction from a distribution system, a minimum pressure of 35 psi under normal operating conditions and 20 psi during emergencies such as firefighting shall be maintained in the distribution system on the low pressure side of the facility.

Mich. Admin. Code R. 325.11015

1979 AC; 2009 AACS