Md. Code Regs. 26.10.17.09

Current through Register Vol. 51, No. 12, June 14, 2024
Section 26.10.17.09 - Release Detection
A. An owner, an operator, and a person in charge of an AST system with a shop-fabricated AST shall provide a method or combination of release detection methods that detect a spill, release, or discharge from the AST system through:
(1) Visual inspections of the AST system in accordance with Regulation .12 of this chapter;
(2) A continuous electronic release detection system; or
(3) A continuous mechanical release detection system.
B. An owner, an operator, and a person in charge of an AST system with a shop-fabricated AST using a continuous electronic or mechanical release detection system shall:
(1) Install, calibrate, operate, and maintain the release detection system in accordance with the manufacturer's instructions; and
(2) At least annually:
(a) Perform routine maintenance on the release detection system;
(b) Check the release detection system for operability at scheduled service checks; and
(c) Per the manufacturer's specifications, inspect, field-test, or calibrate the release detection system to verify that the selected release detection method is being maintained and operated properly to detect a spill, release, or discharge.
C. An owner, an operator, and a person in charge of an AST system with a shop-fabricated AST shall monitor underground piping connected to the AST for spill, releases, and discharges in accordance with COMAR 26.10.05.02D.

Md. Code Regs. 26.10.17.09

Regulation .09 adopted effective 49:12 Md. R. 642, eff. 6/13/2022