Md. Code Regs. 26.10.17.04

Current through Register Vol. 51, No. 12, June 14, 2024
Section 26.10.17.04 - Performance Standards for Vaulted Shop-Fabricated ASTs

An owner, an operator, and a person in charge of an AST system that installs a shop-fabricated AST in a vault shall:

A. Construct a UL listed vault;
B. Ensure the vault and the vaulted AST comply with the design, construction, installation, and operation requirements of:
(1) This regulation;
(2) NFPA 30 "Flammable and Combustible Liquids Code";
(3) If the vaulted AST is used as part of a motor fuel dispensing facility, NFPA 30A "Code for Motor Fuel Dispensing Facilities and Repair Garages"; and
(4) NFPA 70 "National Electrical Code" for all electrical wiring;
C. Ensure the vaulted AST is:
(1) UL listed for aboveground use and for the type of product being stored;
(2) Completely enclosed in the vault; and
(3) Not partially or entirely covered by backfill;
D. Provide venting for the vault and the vaulted AST according to the following requirements:
(1) If the AST stores a Class I liquid, vent the vault in accordance with NFPA 30 "Flammable and Combustible Liquids Code";
(2) Terminate a normal vent for the vaulted AST:
(a) Outside of the vault;
(b) At least 12 feet above ground level; and
(c) At least 5 feet from a building opening;
(3) A normal vent for the vaulted AST may not terminate in a location that allows vapors to be trapped by the eaves of a building;
(4) Ensure that an emergency vent for the vaulted AST is vapor-tight and allows for the venting of vapors inside of the vault; and
(5) Do not use a long-bolt manhole cover as an emergency vent for the vaulted AST;
E. Install vapor and liquid detection systems in the vault that meet the following requirements:
(1) The vapor detection system:
(a) Is equipped with an on-site alarm that has a battery backup;
(b) Has vapor detectors located not higher than 12 inches above the lowest point in the vault; and
(c) Is set to alarm when vapors reach or exceed 25 percent of the lower flammable limit of the oil stored;
(2) The liquid detection system is:
(a) Set to alarm upon detection of a liquid; and
(b) Located in accordance with the liquid detection system manufacturer's instructions; and
(3) The vapor and liquid detection systems required under §E(1) and (2) of this regulation are designed so that if either system alarms, a signal alerts the owner, the operator, and the person in charge of the AST system:
(a) At a constantly attended location where the vaulted AST is located; or
(b) At another location that is continually monitored; and
F. Ensure the vaulted shop-fabricated AST complies with the spill and overfill prevention requirements in Regulation .08 of this chapter.

Md. Code Regs. 26.10.17.04

Regulation .04 adopted effective 49:12 Md. R. 642, eff. 6/13/2022