02-658-110 Me. Code R. § 16

Current through 2024-37, September 11, 2024
Section 658-110-16 - LOW WATER CONTROL FOR SOLID FUEL FIRED BOILERS

Low water protection shall be accomplished in one of two ways:

1. If the opening of an electric circuit will arrest the combustion process, a low water cut-off will be satisfactory if it conforms to the following:
A. All solid fuel fired boilers shall be provided with a properly installed and operating low water cut-off.The low water cut-off may be installed in, or attached to, the boiler at the level recommended by the boiler manufacturer, but in no case shall the low water cut-off be installed below the crown sheet. The low water cut-off, when not installed directly in the boiler, may be installed either in the main supply line (vertical riser) as close to the boiler as possible or in a water column of continuous piping attached directly to the boiler.
B. The low water cut-off shall be designed and approved for the media in which it is used, either steam or water.
C. No valves or other obstructive devices may be installed between the boiler and any safety controls or devices; or
2. If the opening of an electric circuit will not arrest the combustion process, low water protection shall be accomplished in accordance with the appliance manufacturer's instructions.

02-658 C.M.R. ch. 110, § 16