The MAWP on the shell of a power boiler or drum shall be determined by the strength of the weakest course computed from the thickness of the plate, the tensile strength of the plate, the efficiency of the longitudinal joint, the inside diameter of the course, and the factor of safety allowed by Paragraph A. The formula for determining MAWP is as follows:
TStE = MAWP, PSIG
RFS
Where:
TS = Ultimate tensile strength of shell plates, PSI
R = Inside radius of the weakest course of the shell or drum, inches.
t = Minimum thickness of shell plates in weakest course, inches.
E = Efficiency of longitudinal joint, as calculated in the ASME Boiler and Pressure Vessel Code specified in Chapter 11 of the Board's rules.
FS = Factor of Safety allowed by Paragraph A.
02-041 C.M.R. ch. 12, § 5