Possible Sources of Contamination | Minimum Distance (in feet) |
Septic Tanks | 50 |
Storm or Sanitary Sewer | 501 |
Cesspools, outdoor privies, oxidation ponds, subsurface absorption fields, pits, etc. | 1002 |
Sanitary landfills, feed lots, manure piles, solid-waste dumps and similar installations | 100 |
Another water well | 253 |
Drainage canal, ditch, stream, pond or lake | 504 |
1 This distance may be reduced to 30 feet if the sewer is of cast iron with leaded joints or schedule 40 plastic pipe with water-tight joints. 2 For domestic water wells, this distance may be reduced to 50 feet. 3 This minimum distance requirement does not take into consideration the effects of interference from pumping nearby wells in the same aquifer. 4 Horizontally measured from the water edge to the well at the highest water level which may have occurred in a 10 year period. |
La. Admin. Code tit. 56, § I-315