Section V-5080 - Exit from Boiler RoomA. All boiler rooms exceeding 500 square feet floor area and containing one or more boilers having a fuel burning capacity 1,000,000 BTU/hr., or equivalent electrical heat input, shall have at least two means of exit. Each shall be remotely located from the other. Each elevation in such boiler room shall have two means of exit, each remotely located from the other.La. Admin. Code tit. 55, § V-5080
Promulgated by the Department of Public Safety, Office of the State Fire Marshal, LR 33:1368 (July 2007).AUTHORITY NOTE: Promulgated in accordance with R.S. 23:531 and R.S. 51:1424.