La. Admin. Code tit. 55 § V-5073

Current through Register Vol. 50, No. 9, September 20, 2024
Section V-5073 - Boiler Blow Off Equipment
A. The blow down from a boiler that enters a sanitary sewer system or blow down which is considered a hazard to life or property shall pass through some form of blow off equipment that will reduce the pressure leaving the blow down equipment to not more than 5 psi, and the temperature to no more then 150° F.
B. All blow off equipment shall be fitted with openings to facilitate cleaning and inspection and shall conform to the recommended rules for National Board Boiler Blow off Equipment.

La. Admin. Code tit. 55, § V-5073

Promulgated by the Department of Public Safety, Office of the State Fire Marshal, LR 33:1367 (July 2007).
AUTHORITY NOTE: Promulgated in accordance with R.S. 23:531 and R.S. 51:1424.