La. Admin. Code tit. 51 § XIV-809

Current through Register Vol. 50, No. 9, September 20, 2024
Section XIV-809 - Limitations
A. The following limitations/requirements shall apply to indirect waste pipes.
1. Indirect waste piping exceeding 2 ft (610 mm) long shall be trapped.
2. The maximum length of the indirect waste to indirect waste receptor shall not exceed 15-feet (4527 mm). Should an indirect waste pipe exceed 15 feet in length, a local vent shall be provided at a maximum of every 15 feet in length.
B. Cleaning. Indirect waste piping shall be so installed as to permit ready access for flushing and cleansing.

La. Admin. Code tit. 51, § XIV-809

Promulgated by the Department of Health and Hospitals, Office of Public Health, LR 38:2858 (November 2012).
AUTHORITY NOTE: Promulgated in accordance with R.S. 40:4(A)(7) and R.S. 40:5(2)(3)(7)(9)(16)(17)(20).