La. Admin. Code tit. 51 § XIV-1115

Current through Register Vol. 50, No. 9, September 20, 2024
Section XIV-1115 - Values for Continuous Flow
A. Where there is a continuous or semicontinuous discharge into the building storm drain or building storm sewer, as from a pump, ejector, air conditioning plant, or similar device, each gallon per minute of such discharge shall be computed as being equivalent to 24 sq ft (2.23 m2) of roof area, based upon a 4-inch (102 mm) rainfall.

La. Admin. Code tit. 51, § XIV-1115

Promulgated by the Department of Health and Hospitals, Office of Public Health, LR 38:2880 (November 2012).
AUTHORITY NOTE: Promulgated in accordance with R.S. 40:4(A)(7) and R.S. 40:5(2)(3)(7)(9)(16)(17)(20).