Current through Register Vol. 50, No. 9, September 20, 2024
Section XIII-1911 - Service Lines: Installation [49 CFR 192.361]A. Depth. Each buried service line must be installed with at least 12 inches (305 millimeters) of cover in private property and at least 18 inches (457 millimeters) of cover in streets and roads. However, where an underground structure prevents installation at those depths, the service line must be able to withstand any anticipated external load. [ 49 CFR 192.361(a)]B. Support and Backfill. Each service line must be properly supported on undisturbed or well-compacted soil, and material used for backfill must be free of materials that could damage the pipe or its coating. [ 49 CFR 192.361(b)]C. Grading for Drainage. Where condensate in the gas might cause interruption in the gas supply to the customer, the service line must be graded so as to drain into the main or into drips at the low points in the service line. [ 49 CFR 192.361(c)]D. Protection against Piping Strain and External Loading. Each service line must be installed so as to minimize anticipated piping strain and external loading. [ 49 CFR 192.361(d)]E. Installation of Service Lines into Buildings. Each underground service line installed below grade through the outer foundation wall of a building must: [ 49 CFR 192.361(e)] 1. in the case of a metal service line, be protected against corrosion; [ 49 CFR 192.361(e)(1)]2. in the case of a plastic service line, be protected from shearing action and backfill settlement; and [ 49 CFR 192.361(e)(2)]3. be sealed at the foundation wall to prevent leakage into the building. [ 49 CFR 192.361(e)(3)]F. Installation of Service Lines under Buildings. Where an underground service line is installed under a building: [ 49 CFR 192.361(f)] 1. it must be encased in a gas-tight conduit; [ 49 CFR 192.361(f)(1)]2. the conduit and the service line must, if the service line supplies the building it underlies, extend into a normally usable and accessible part of the building; and [ 49 CFR 192.361(f)(2)]3. the space between the conduit and the service line must be sealed to prevent gas leakage into the building and, if the conduit is sealed at both ends, a vent line from the annular space must extend to a point where gas would not be a hazard, and extend above grade, terminating in a rain and insect resistant fitting. [ 49 CFR 192.361(f)(3)]G. Locating Underground Service Lines. Each underground nonmetallic service line that is not encased must have a means of locating the pipe that complies with §1721. E [ 49 CFR 192.361(g)]La. Admin. Code tit. 43, § XIII-1911
Promulgated by the Department of Natural Resources, Office of Conservation, LR 9:234 (April 1983), amended LR 10:526 (July 1984), LR 27:1543 (September 2001), LR 30:1249 (June 2004).AUTHORITY NOTE: Promulgated in accordance with R.S. 30:501 et seq.