La. Admin. Code tit. 43 § XIII-1903

Current through Register Vol. 50, No. 9, September 20, 2024
Section XIII-1903 - Customer Meters and Regulators: Location [49 CFR 192.353]
A. Each meter and service regulator whether inside or outside of a building, must be installed in a readily accessible location and be protected from corrosion and other damage, including, if installed outside a building, vehicular damage that may be anticipated. However, the upstream regulator in a series may be buried. [ 49 CFR 192.353(a)]
B. Each service regulator installed within a building must be located as near as practical to the point of service line entrance. [ 49 CFR 192.353(b)]
C. Each meter installed within a building must be located in a ventilated place and not less than 3 feet (914 millimeters) from any source of ignition or any source of heat which might damage the meter. [ 49 CFR 192.353(c)]
D. Where feasible, the upstream regulator in a series must be located outside the building, unless it is located in a separate metering or regulating building. [ 49 CFR 192.353(d)]

La. Admin. Code tit. 43, § XIII-1903

Promulgated by the Department of Natural Resources, Office of Conservation, LR 9:233 (April 1983), amended LR 10:526 (July 1984), LR 27:1543 (September 2001), LR 30:1248 (June 2004).
AUTHORITY NOTE: Promulgated in accordance with R.S. 30:501 et seq.