Section V-4519 - Monitoring and Inspections
A. The owner or operator must conduct, as a minimum, the following monitoring and inspections when incinerating hazardous waste:
1. monitoring of instruments which relate to combustion and emission control (e.g., those instruments measuring waste feed, auxiliary fuel feed, air flow, incinerator temperature, scrubber flow, scrubber pH, and relevant level controls) at least every 15 minutes. Appropriate corrections to maintain steady state combustion conditions must be made immediately either automatically or by the operator; and
2. daily inspection of the complete incinerator and associated equipment (e.g., pumps, valves, conveyors, pipes, etc.) for leaks, spills, and fugitive emissions. Also, all emergency shutdown controls and system alarms must be inspected daily to assure proper operation.

La. Admin. Code tit. 33, § V-4519

Promulgated by the Department of Environmental Quality, Office of Solid and Hazardous Waste, Hazardous Waste Division, LR 10:200 (March 1984).