RELATES TO: KRS 58.200, 162.062, 318.160
NECESSITY, FUNCTION, AND CONFORMITY: KRS 318.130 requires the department to promulgate administrative regulations establishing the Kentucky State Plumbing Code regulating the construction, installation, and alteration of plumbing and plumbing fixtures and appliances, house sewers and private water supplies, and the methods and materials that may be used in Kentucky. This administrative regulation establishes the minimum plumbing fixture requirements for buildings in Kentucky.
Occupancy Group | Examples | Water Closet (males)a | Water Closet (females)a | Lavatories (male)a | Lavatories (female)a | Drinking Fountainb | Urinals (males)a |
A-1 | Theaters, movie theaters, and similar buildings | 1 per up to 100; 2 for 101 to 200; 3 for 201 to 400; 1 per additional 500 afterwards | 1 for up to 50; 2 for 51 to 100; 3 for 101 to 150; 4 for 151 to 200; 1 per additional 150 afterwards | 1 for up to 100; 2 for 101 to 200; 3 for 201 to 400; 4 for 401 to 750; 1 per each 500 afterwards | 1 for up to 100; 2 for 101 to 200; 3 for 201 to 400; 4 for 401 to 750; 1 per each 500 afterwards | 1 per 500 on every floor | 1 for 11 to 100; 2 for 101 to 300; 3 for 301 to 600; and 1 for each additional 300 afterward |
A-2 | Banquet halls, casinos, dance halls, night clubs, restaurants, cafeterias, taverns, and bars | 1 per up to 200; 2 for 201 to 400; 1 per additional 200 afterwards | 1 per up to 100; 2 for 101 to 200; 1 per additional 200 afterwards | 1 per 200 | 1 per 200 | 1 per 100 unless water stations are provided | 1 for 50 to 200; 1 per additional 150 afterwards |
A-3 | Libraries, museums, and art galleries | 1 per 200 | 1 per 100 | 1 per 200 | 1 per 100 | 1 per 500 | 1 for 11 to 200; 2 for 201 to 400; 3 for 401 to 600; and 1 for each additional 300 afterward |
Assembly halls and similar buildings | 1 per up to 100; 2 for 101 to 200; 3 for 201 to 400; 1 per additional 500 afterwards | 1 for up to 50; 2 for 51 to 100; 3 for 101 to 150; 4 for 151 to 200; 1 per additional 150 afterwards | 1 for up to 100; 2 for 101 to 200; 3 for 201 to 400; 4 for 401 to 750; 1 per each 500 afterwards | 1 for up to 100; 2 for 101 to 200; 3 for 201 to 400; 4 for 401 to 750; 1 per each 500 afterwards | 1 per 500 on every floor | 1 for 11 to 100; 2 for 101 to 300; 3 for 301 to 600; and 1 for each additional 300 afterward | |
Places of worship | 1 per 300 | 1 per 150 | 1 per 200 | 1 per 200 | 1 per 400 | 1 for 50 to 150; 1 for each additional 150 afterwards | |
A-4 | Structures for indoor sporting events and activities | 1 for 100; 2 for 101 to 200; 3 for 201 to 400; 1 per additional 500 afterwards | 1 for 50; 2 for 51 to 100; 3 for 101 to 150; 4 for 151 to 200; 1 per additional 150 afterwards | 1 for up to 100; 2 for 101 to 200; 3 for 201 to 400;4 for 401 to 750; 1 per each 500 afterwards | 1 for up to 100; 2 for 101 to 200; 3 for 201 to 400;4 for 401 to 750; 1 per each 500 afterwards | 1 per 500 on every floor | 1 for 11 to 100; 2 for 101 to 300; 3 for 301 to 600; and 1 for each additional 300 afterward |
A-5 | Stadiums and other structures for outdoor sporting events and activities | 1 for 100; 2 for 101 to 200; 3 for 201 to 400; 1 per additional 500 afterwards | 1 for 50; 2 for 51 to 100; 3 for 101 to 150; 4 for 151 to 200; 1 per additional 150 afterwards | 1 for up to 100; 2 for 101 to 200;3 for 201 to 400;4 for 401 to 750; 1 per each 500 afterwards | 1 for up to 100; 2 for 101 to 200;3 for 201 to 400;4 for 401 to 750; 1 per each 500 afterwards | 1 per 500 on every floor | 1 for 11 to 100; 2 for 101 to 300; 3 for 301 to 600; and 1 for each additional 300 afterward |
B | Swimming pool bathhouses | 1 per 75 | 1 per 50 | 1 per 50 | 1 per 50 | 1 per 200 | 1 per 75 |
Park service buildings or bathhouses | See subsections (11) and (12) of this section | ||||||
Office buildingsc | 1 for 1 to 15; 2 for 16 to 35; 3 for 36 to 55; 4 for 56 to 80; 5 for 81 to 110; 6 for 111 to 150; 1 for each additional 40 afterwards | 1 for 1 to 15; 2 for 16 to 35; 3 for 36 to 60; 4 for 61 to 90; 5 for 91 to 125; 1 for each additional 75 afterwards | 1 per 75 | Optional | |||
Schools of higher-education and similar educational facilities | 1 per 50 | 1 per 25 | 1 per 25 | 1 per 25 | 1 per 75 | 1 per 50 | |
E | School buildings (not including higher-education facilities | 1 for up to 25; 2 for 26 to 100; 1 for each 100 afterwards | 2 for up to 25; 3 for 26 to 50; 6 for 51 to 100; 8 101 to 200; 10 for 201 to 300; 12 for 301 to 400; 14 for 401 to 500; 1 additional for each 40 afterwards | 1 per 25 up to 50; 1 per 50 afterwards | 1 per 25 up to 50; 1 per 50 afterwards | See subsection (10) of this section | 1 for 1 to 25; 2 for 26 to 50; 4 for 51 to 100; 6 for 101 to 200; 8 for 201 to 300; 10 for 301 to 400; 12 for 401 to 500; 1 for each additional 50 afterwards |
M | Mercantile and retail food store | 1 per 150 up to 450; 1 per additional 500 | 1 per 100 up to 400; 1 per each additional 300 | 1 for 1 to 200; 2 for 201 to 400; 3 for 401 to 700; 1 for each additional 500 | 1 for 1 to 200; 2 for 201 to 400; 3 for 401 to 700; 1 for each additional 500 | 1 per 500 on each floor | 1 for 50 to 200; 2 for 201 to 400; 3 for 401 to 600; 1 for additional 300 afterwards |
R-1 | Transient lodging facilities (public service areas) | 1 per 25 | 1 per 15 | 1 per 25 | 1 per 25 | 1 per 75 on each floor | 1 for 11 to 100; 1 for each additional 50 afterwards |
Transient lodging facilities (without private bath) | 1 per 10; 1 per additional 25 afterwards | 1 per 8; 1 per additional 20 afterwards | 1 per 10 | 1 per 10 | 1 per 75 on each floor | 1 for 11 to 100; 1 for each additional 50 afterwards | |
R-2 c | Dormitories, fraternities, sororities, and rooming houses | 1 per 10 | 1 per 10 | 1 per 75 | Optional | ||
R-3 c | Congregate living facilities with 16 or fewer persons | 1 per 10 | 1 per 10 | 1 per 75 | Optional | ||
R-4 c | Congregate living facilities with 16 or fewer persons | 1 per 10 | 1 per 10 | 1 per 75 | Optional | ||
I-1 | Residential Care | 1 per 10 | 1 per 10 | 1 per 10 | 1 per 10 | 1 per 100 on each floor | 1 for each 50 |
I-2 | Hospitals wards and nursing home wards | 1 per 10 | 1 per 10 | 1 per 10 | 1 per 10 | 1 per 100 on each floor | 1 for each 50 |
Hospital individual rooms and nursing home individual roomsc | 1 per room | 1 per room | Optional | Optional | |||
I-3 | Institutions, penal (Cells) c | 1 prison-type water closet per cell | 1 prison-type lavatory per cell | Optional | Optional | ||
Institutions, penal. (Day rooms and dorms) | 1 per 12 | 1 per 8 | 1 per 12 | 1 per 12 | 1 per floor | Optional | |
I-4 | Adult day care and child day care | 1 per 10 | 1 per 10 | 1 per 10 | 1 per 10 | 1 per 100 on each floor | 1 for each 50 |
F-1 and F-2 | Workshops and factories | 1 for 25 to 100; 1 for each additional 30 afterwards | 1 for 15 to 100; 1 for each additional 30 afterwards | 1 for 25 to 100; 1 for each additional 50 afterwards | 1 for 25 to 100; 1 for each additional 50 afterwards | 1 for 50 to 100 on each floor; 1 for each additional 75 afterwards | 1 for 11 to 50; 2 for 51 to 100; 1 for each additional 100 afterward |
S-2 | Parking garagesd | 1 | 1 | 1 | 1 | Optional | 1 |
Notes: a. The ratio equals the number of fixtures per the number of male occupants or female occupants. b. The ratio equals the number of fixtures per the total number of occupants. c. Separate male and female water closets or male and female lavatories are not required in these occupancy types. d. There are no minimum fixture requirements for Group S-1 or S-2 buildings except for the minimum fixture requirement for parking garages. |
815 KAR 20:191
STATUTORY AUTHORITY: KRS 198B.040(10), 318.130