675 Ind. Admin. Code 17-1.8-25

Current through September 4, 2024
Section 675 IAC 17-1.8-25 - Section 680.26(B)(1); conductive pool shells

Authority: IC 22-13-2-2; IC 22-13-2-13

Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15; IC 36-7

Sec. 25.

(a) After the first sentence of 680.26(B)(1)(a), insert a new sentence to read as follows: Reinforcing steel shall not extend into soil beyond the concrete envelope.
(b) After 680.26(B)(1)(b), insert an exception to read as follows: Exception to (b): The equipotential bonding grid shall not be required to be installed under the bottom or vertically along the walls of vinyl lined polymer wall, fiberglass composite, or other pools constructed of nonconductive materials.

675 IAC 17-1.8-25

Fire Prevention and Building Safety Commission; 675 IAC 17-1.8-25; filed Jul 27, 2009, 10:39 a.m.: 20090826-IR-675090140FRA
Readopted filed 7/17/2015, 3:40 p.m.: 20150812-IR-675140473RFA
Readopted filed 7/8/2021, 3:18 p.m.: 20210804-IR-675210166RFA

Agency cited as 675 IAC 17-1.8-28, which was renumbered by the Publisher as 675 IAC 17-1.8-25.