410 Ind. Admin. Code 6-7.2-18

Current through November 6, 2024
Section 410 IAC 6-7.2-18 - Infirmary

Authority: IC 16-19-3-4

Affected: IC 16-19-3

Sec. 18.

(a) Youth camps constructed after the effective date of this rule shall include a separate room with toilet and lavatory facilities to be used as an infirmary and isolation area.
(b) The separate room described in subsection (a) shall have the following:
(1) Ventilation to keep it free of excessive heat, condensation, vapors, noxious odors, and fumes.
(2) Heating equipment capable of maintaining a temperature of at least sixty-eight (68) degrees Fahrenheit.
(3) At least one (1) cot per one hundred (100) campers and staff, with a minimum of two (2) cots.
(4) At least one (1) adult shall be present when campers are in the infirmary.
(5) At least seventy (70) foot-candles of light measured thirty (30) inches from the floor.

410 IAC 6-7.2-18

Indiana State Department of Health; 410 IAC 6-7.2-18; filed Jun 27, 2002, 1:30 p.m.: 25 IR 3750; readopted filed Jul 14, 2008, 2:14 p.m.: 20080806-IR-410080322RFA
Readopted filed 9/10/2014, 2:08 p.m.: 20141008-IR-410140299RFA