410 Ind. Admin. Code 33-4-4

Current through December 25, 2024
Section 410 IAC 33-4-4 - Temperature and relative humidity

Authority: IC 16-19-3-4; IC 16-41-37.5

Affected: IC 16-41-37.5

Sec. 4.

(a) Heating facilities shall be capable of and shall be operated to maintain a temperature during periods of student occupancy not less than the following:
(1) Sixty-eight (68) degrees Fahrenheit (F) in all:
(A) instructional rooms;
(B) offices;
(C) locker rooms; and
(D) cafeterias.
(2) Sixty-five (65) degrees Fahrenheit in activity rooms and shops.
(3) Sixty (60) degrees Fahrenheit in interior toilet rooms.
(b) Where provided air-conditioning systems shall be capable of providing and shall be operated to maintain a temperature not to exceed seventy-eight (78) degrees Fahrenheit and sixty-five percent (65%) relative humidity during periods of student occupancy.

410 IAC 33-4-4

Indiana State Department of Health; 410 IAC 33-4-4; filed Apr 13, 2011, 11:18 a.m.: 20110511-IR-410090682FRA
Readopted filed 9/13/2017, 4:08 p.m.: 20171011-IR-410170339RFA
Readopted filed 11/28/2023, 11:52 a.m.: 20231227-IR-410230647RFA