Authority: IC 15-16-1-6; IC 15-16-1-7
Affected: IC 15-16-1-10
Sec. 1.
The minimum required rate of discharge in cubic feet per minute of air at one hundred twenty percent (120%) of the maximum permitted start-to-discharge pressure for pressure relief valves to be used on containers other than those constructed in accordance with DOT specifications shall be as follows:
Surface Area Square Feet | Flow Rate CFM Air |
20 | 258 |
25 | 310 |
30 | 360 |
35 | 408 |
40 | 455 |
45 | 501 |
50 | 547 |
55 | 591 |
60 | 635 |
65 | 678 |
70 | 720 |
75 | 762 |
80 | 804 |
85 | 845 |
90 | 885 |
95 | 925 |
100 | 965 |
105 | 1,010 |
110 | 1,050 |
115 | 1,090 |
120 | 1,120 |
125 | 1,160 |
130 | 1,200 |
135 | 1,240 |
140 | 1,280 |
145 | 1,310 |
150 | 1,350 |
155 | 1,390 |
160 | 1,420 |
165 | 1,460 |
170 | 1,500 |
175 | 1,530 |
180 | 1,570 |
185 | 1,600 |
190 | 1,640 |
195 | 1,670 |
200 | 1,710 |
210 | 1,780 |
220 | 1,850 |
230 | 1,920 |
240 | 1,980 |
250 | 2,050 |
260 | 2,120 |
270 | 2,180 |
280 | 2,250 |
290 | 2,320 |
300 | 2,380 |
310 | 2,450 |
320 | 2,510 |
330 | 2,570 |
340 | 2,640 |
350 | 2,700 |
360 | 2,760 |
370 | 2,830 |
380 | 2,890 |
390 | 2,950 |
400 | 3,010 |
450 | 3,320 |
500 | 3,620 |
550 | 3,910 |
600 | 4,200 |
650 | 4,480 |
700 | 4,760 |
750 | 5,040 |
800 | 5,300 |
850 | 5,590 |
900 | 5,850 |
950 | 6,120 |
1,000 | 6,380 |
1,050 | 6,640 |
1,100 | 6,900 |
1,150 | 7,160 |
1,200 | 7,400 |
1,250 | 7,660 |
1,300 | 7,910 |
1,350 | 8,160 |
1,400 | 8,410 |
1,450 | 8,650 |
1,500 | 8,900 |
1,550 | 9,140 |
1,600 | 9,380 |
1,650 | 9,620 |
1,700 | 9,860 |
1,750 | 10,090 |
1,800 | 10,330 |
1,850 | 10,560 |
1,900 | 10,800 |
1,950 | 11,030 |
2,000 | 11,260 |
2,050 | 11,490 |
2,100 | 11,720 |
2,150 | 11,950 |
2,200 | 12,180 |
2,250 | 12,400 |
2,300 | 12,630 |
2,350 | 12,850 |
2,400 | 13,080 |
2,450 | 13,300 |
2,500 | 13,520 |
Area = overall length in feet times outside diameter in feet times 3.1416
Area = (overall length in feet plus 0.3 outside diameter in feet) times outside diameter in feet times 3.1416
Area = outside diameter in feet squared times 3.1416
The rate of discharge may be interpolated for intermediate values of surface area. For containers with a total outside surface area greater than two thousand five hundred (2,500) square feet, the required flow rate can be calculated using the formula, Flow Rate CFM Air = 22.11 A0.82, where A = outside surface area of the container in square feet.
355 IAC 3-9-1