Sec. 2.1.
For systems that *** | The system must determine *** |
(A) Use only one (1) point of disinfectant application | (i) One (1) inactivation ratio (CTcalc/CT99.9) before or at the first customer during peak hourly flow or (ii) Successive CTcalc/CT99.9 values, representing sequential inactivation ratios, between the point of disinfectant application and a point before or at the first customer during peak hourly flow. Under this alternative, systems must calculate the total inactivation ratio by determining (CTcalc/CT99.9) for each sequence and then adding the (CTcalc/CT99.9) values together to determine (3CTcalc/CT99.9). |
(B) Use more than one (1) point of disinfectant application before the first customer | The (CTcalc/CT99.9) value of each disinfection segment immediately prior to the next point of disinfectant application, or, for the final segment, before or at the first customer during peak hourly flow using the procedure specified in (A)(ii) of this table. |
327 IAC 8-2.6-2.1