Authority: IC 13-13-5; IC 13-14-8-7; IC 13-14-9; IC 13-18-3; IC 13-18-16
Affected: IC 13-18
Sec. 4.1.
Contaminant | MCL (mg/l) | Methodology | Detection Limit (mg/l) |
Antimony | 0.006 | Atomic absorption; furnace | 0.003 |
Atomic absorption; platform | 0.00085 | ||
ICP-mass spectrometry | 0.0004 | ||
Hydride-atomic absorption | 0.001 | ||
Arsenic | 0.0106 | Atomic absorption; furnace | 0.001 |
Atomic absorption; platform - stabilized temperature | 0.00057 | ||
Atomic absorption; gaseous hydride | 0.001 | ||
ICP-mass spectrometry | 0.00148 | ||
Asbestos | 7 MFL1 | Transmission electron microscopy | 0.01 MFL |
Barium | 2 | Atomic absorption; furnace | 0.002 |
Atomic absorption; direct aspiration | 0.1 | ||
Inductively coupled plasma | 0.002 (0.001) | ||
Beryllium | 0.004 | Atomic absorption; furnace | 0.0002 |
Atomic absorption; platform | 0.000025 | ||
Inductively coupled plasma2 | 0.0003 | ||
ICP-mass spectrometry | 0.0003 | ||
Cadmium | 0.005 | Atomic absorption; furnace | 0.0001 |
Inductively coupled plasma | 0.001 | ||
Chromium | 0.1 | Atomic absorption; furnace | 0.001 |
Inductively coupled plasma | 0.007 (0.001) | ||
Cyanide | 0.2 | Distillation, spectrophotometric3 | 0.02 |
Distillation, automated spectrophotometric 3 | 0.005 | ||
Distillation, selective electrode3 | 0.05 | ||
Distillation, amenable, spectrophotometric4 | 0.02 | ||
Fluoride | 4.0 | Colorimetric SPADNS; with distillation | 0.1 |
Potentiometric ion selective electrode | 0.1 | ||
Automated alizarin fluoride blue; with distillation (complexone) | 0.05 | ||
Automated ion selective electrode | 0.1 | ||
Mercury | 0.002 | Manual cold vapor technique | 0.0002 |
Automated cold vapor technique | 0.0002 | ||
Nitrate | 10 (as N) | Manual cadmium reduction | 0.01 |
Automated hydrazine reduction | 0.01 | ||
Automated cadmium reduction | 0.05 | ||
Ion selective electrode | 1 | ||
Ion chromatography | 0.01 | ||
Nitrite | 1 (as N) | Spectrophotometric | 0.01 |
Automated cadmium reduction | 0.05 | ||
Manual cadmium reduction | 0.01 | ||
Ion chromatography | 0.004 | ||
Selenium | 0.05 | Atomic absorption; furnace | 0.002 |
Atomic absorption; gaseous hydride | 0.002 | ||
Thallium | 0.002 | Atomic absorption; furnace | 0.001 |
Atomic absorption; platform | 0.00075 | ||
ICP-mass spectrometry | 0.0003 |
preconcentration.
indicate the MCL has been exceeded, the commissioner may require that one (1) additional sample be collected as soon as possible after the initial sample was taken (but not to exceed two (2) weeks) at the same sampling point.
is determined by a running annual average at each sampling point. If the average at any sampling point is greater than the MCL, then the system is out of compliance. If any one (1) sample would cause the annual average to be exceeded, then the system is out of compliance immediately. Any sample below the method detection limit shall be calculated at zero (0) for the purpose of determining the annual average. If a system fails to collect the required number of samples, compliance (average concentration) will be based on the total number of samples collected.
if the level of a contaminant at any sampling point is greater than the MCL. If a confirmation sample is required by the commissioner, the determination of compliance will be based on the annual average of the initial MCL exceedance and any commissioner-required confirmation samples. If a system fails to collect the required number of samples, compliance (average concentration) will be based on the total number of samples collected.
under this section shall be conducted using the sample preservation, container, and maximum holding time procedures specified in the following table:
Contaminant | Preservative3 | Container1 | Time2 |
Antimony | HNO3 | P or G | 6 months |
Arsenic | HNO3 | P or G | 6 months |
Asbestos | 4°C | P or G | 48 hours4 |
Barium | HNO3 | P or G | 6 months |
Beryllium | HNO3 | P or G | 6 months |
Cadmium | HNO3 | P or G | 6 months |
Chromium | HNO3 | P or G | 6 months |
Cyanide | 4°C, NaOH | P or G | 14 days |
Fluoride | none | P or G | 1 month |
Mercury | HNO3 | P or G | 28 days |
Nickel | HNO3 | P or G | 6 months |
Nitrate | 4°C | P or G | 48 hours5 |
Nitrate-nitrite6 | H2SO4 | P or G | 28 days |
Nitrite | 4°C | P or G | 48 hours |
Selenium | HNO3 | P or G | 6 months |
Thallium | HNO3 | P or G | 6 months |
days.
327 IAC 8-2-4.1