Current through November 6, 2024
Section 327 IAC 3-6-17 - Inverted siphonsAuthority: IC 13-13-5; IC 13-14-8; IC 13-14-9; IC 13-15-1-2; IC 13-15-2-1; IC 13-18-2
Affected: IC 13-11-2; IC 13-15; IC 13-18
Sec. 17.
(a) Inverted siphons shall have: (1) not less than two (2) barrels; and(2) a minimum pipe size of six (6) inches in diameter.(b) The minimum design velocity, at average flow, shall be three (3) feet per second measured at a point immediately preceding the outlet.Water Pollution Control Board; 327 IAC 3-6-17; filed May 17, 1999, 12:11 p.m.: 22 IR 3094; readopted filed Apr 11, 2005, 2:45 p.m.: 28 IR 2470; readopted filed Jun 15, 2011, 11:15 a.m.: 20110713-IR-327110193BFAReadopted filed Jun 29, 2017, 9:34 a.m.: 20170726-IR-327170225BFA)Readopted filed 5/12/2023, 1:07 p.m.: 20230607-IR-327230079BFA