105 Ind. Admin. Code 16-1-8

Current through October 2, 2024
Section 105 IAC 16-1-8 - Requirements for installation of conduit

Authority: IC 8-23-2-6; IC 8-23-5-10

Affected: IC 8-23-5-10

Sec. 8.

(a) All conduits must have a minimum depth of cover of four (4) feet, including under ditches. All lines must be a minimum of two (2) feet below any buried drainage structure or improvement. All conduits shall be stubbed out a minimum of two (2) inches into each handhole.
(b) All conduits shall be installed pursuant to the approved permit plans and specifications.
(c) Conduit shall be installed underground by means of trenching or directional drilling.
(d) Warning tape shall be furnished and installed in all the trenches containing conduit, as shown on the approved permit plans.
(e) Conduit shall be placed two (2) feet from the department's right-of-way fence line and within the right-of-way.

105 IAC 16-1-8

Indiana Department of Transportation; 105 IAC 16-1-8; emergency rule filed 12/16/2021, 12:43 p.m.: 20211222-IR-105210537ERA, eff Jan 1, 2022