Time (minutes) required for last 6 inches of water to fall | FOR RESIDENTIAL USE Required Absorption Area (sq ft)/bedroom) | FOR INSTITUTIONAL OR COMMERCIAL USE Allowable application rate (GPD/sq ft) (5) | Recommended depth from bottom of the trench to the limiting layer | |
18 - 60 | 200 | 1.0 | ||
90 | 210 | .95 | 3 feet | |
120 | 235 | .85 | ||
150 | 265 | .75 | ||
180 | 290 | .69 | ||
240 | 320 | .62 | ||
300 | 350 | .57 | 2 feet | |
360 | 385 | .52 | ||
NOTE: | ||||
1. | Absorption area is figured as trench bottom area in absorption trenches and bottom area in seepage beds. | |||
2. | Seepage beds require 11/2 times the seepage field absorption area specified. | |||
3. | Over 360 is unsuitable for subsurface seepage systems. | |||
4. | Under 18 is unsuitable for subsurface seepage systems. | |||
5. | Divide the required total gallons per day by this number to get the number of square feet required |
Ill. Admin. Code tit. 77, pt. 905, app A, ILLUSTRATION H, exh. A