TYPES OF PIPES | ASTM STANDARD | BUILDING SEWER 1 OR COMMON COLLECTOR | SEWER LINES 1 | ALL SUBSURFACE SEEPAGE SYSTEMS | ||
5 ft. from building to septic-aeration tank to 5 ft. beyond the septic tank, aeration tank or distribution box | Additional treatment facilities and sand filter distribution lines and collection lines | |||||
ABS | (DWV Schedule 40) | F628-06 | x | x | x | |
ABS | (DWV Schedule 40) | D2661-06 | x | x | x | |
ABS | D1527-99 (2005) | x | x | x | ||
ABS | (Sewer Pipe) | D2751-05 | x2 | x2 | x2 | |
PVC | D1785-06 | x | x | x | ||
PVC | (DWV Schedule 40) | D2665-07 | x | x | x | |
PVC | (DWV Schedule 40) | F891-04 | x | x | x | |
PVC | (Type PSM) (SDR 35) | D3034-06 | x2 | x2 | x2 | |
PVC | (Sewer & Drain PS-50) | F891-04 | x | x | x | |
PVC | (Sewer & Drain PS-25) | F891-04 | x | x | ||
PVC | (Corrugated-Smoothwall) | F949-06 | x | x | ||
PVC | (Std. or Perforated) | D2729-03 | x | x | ||
PE | (Smoothwall) | R810-07 AASHTO Standard M252-06 | x | x | ||
PE | (Corrugated-Perforated) | F405-05 (Heavy Duty Only) | x | |||
PE | (Corrugated-(Perforated) | F667-06 | x |
x - Indicates approved use.
l Plastic materials shall not be co-mingled within this area except through the use of proper adapters. (See Illinois Plumbing Code.) When the building sewer is of a type of material that is different from the building drain, proper transition fittings shall be used.
2 Pipe shall be SDR (Standard Dimension Ratio) 35 only.
Note: The last 2 numbers of the ASTM Standard indicate the date of the edition.
Ill. Admin. Code tit. 77, pt. 905, app A, ILLUSTRATION C