Structures used as barns shall be classified as follows:
Class A - Walls and roof of noncombustible materials. Stall dividers of noncombustible material or two-inch dimension hardwood lumber. Use of combustible kick boards shall not cause otherwise noncombustible stall dividers to be classed as combustible.
Class B - Walls masonry; roof of combustible materials.
Class C - Walls and roof of combustible material.
Barn Size Limitations
Maximum Building Area in Square Feet
Construction Class | Non Sprinklered | Sprinklered |
A | Unlimited | Unlimited |
B | Not Permitted | 18,000 |
C | Not Permitted | 12,000 |
Spacing Between Barns in Feet
Types of Facing-Walls | Masonry | |
Masonry | 25 | Noncombustible |
Noncombustible | 25 | 35 |
Combustible | 35 | 50 |
Ill. Admin. Code tit. 41, § 150.50