Ill. Admin. Code tit. 35 § 653.106

Current through Register Vol. 48, No. 45, November 8, 2024
Section 653.106 - Distribution System Pressure
a) Distribution system design shall conform to the Standards.
b) Distribution systems shall be designed to maintain a minimum pressure of 20 psi measured at the ground surface in all parts of the system under fire-fighting demand or other similar emergency operating conditions.

Ill. Admin. Code tit. 35, § 653.106