Current through Register Vol. 49, No. 2, January 10, 2025
Section 604.1305 - Overflowa) All water storage structures must be provided with an overflow that is brought down to an elevation between 12 and 24 inches above the ground surface and that discharges over a drainage inlet structure or a splash plate.b) No overflow may be connected directly to a sewer or a storm drain.c) All overflow pipes must be located so that any discharge is visible.d) Overflow for a ground level storage reservoir must meet the following requirements: 1) open downward and be screened with 24 mesh non-corrodible screen; and2) when a flapper or duckbill valve is used, a screen must be provided inside the pipe.e) Overflow for an elevated tank must: 1) open downward and be screened with a 4 mesh, non-corrodible screen or mechanical device; and2) when a flapper or duckbill valve is used, a screen must be provided inside the pipe.f) The overflow pipe must be of sufficient diameter to permit waste of water in excess of the filling rate.Ill. Admin. Code tit. 35, § 604.1305
Adopted in R18-17 at 43 Ill. Reg. 8064, effective 7/26/2019.