Source of Contamination | Distance for Clay or Loam Soils | Distances for Soils with Higher Permeability than Clay or Loam |
Cesspools, leaching sewage disposal pits | 150' | 300' |
Privies | 150' | 300' |
Septic tanks and subsurface septic tanks effluent disposal tile | 75' | 150' |
Livestock, grazing areas or feedlots | 50' | 100' |
Sewers (non-watertight) | 50' | 50' |
Sewers (cast iron pipe, with leaded or mechanical joints) | 25' | 25' |
Sewers (extra-heavy cast iron pipe, asbestos-cement pressure pipe, prestressed concrete pipe, or PVC (polyvinyl chloride) pipe meeting water main standards, with pressure tested, leaded, mechanical or slip-on joints | 10' | 10' |
Washwater sumps of reinforced concrete construction | 10' | 10' |
Flood waters - A horizontal distance must be maintained by natural earth or fill. In addition, wells must meet the requirements of Section 604.240(k). | 15'* | 15'* |
Flood waters - A vertical distance must be maintained to which structure and earth protection must be carried above maximum high water elevation. In addition, wells must meet the requirements of Section 604.240(k). | 2' | 2' |
Fuel storage tanks above ground | 25'** | 25'** |
* The Agency must consider special structural arrangements equivalent to earthen construction for protection of the well when horizontal earth protection is impractical. | ||
** unless otherwise approved by the Agency under Section 604.145(b) |
Ill. Admin. Code tit. 35, § 604.150