All land application systems must provide adequate storage, with adequacy being determined using either of the following methods, except that those facilities that do not generate wastewater year round must use Method I:
Adequate storage shall be based on a rational design that must include capacity for the wettest year with a 20-year return frequency. The volume provided shall be sufficient to hold flows received during the following periods:
The minimum storage capacity, by volume, shall be capable of storing at least 150 days production of wastewater, at design average flow, except that in southern Illinois areas (defined as all areas south of Interstate 70) a minimum of 120 days storage capacity shall be provided.
The storage lagoon must be designed and constructed in accordance with 35 Ill. Adm. Code 370, Illinois Recommended Standards for Sewage Works.
Ill. Admin. Code tit. 35, § 372.420