Section 24.39.30.600 - IDAHO BUILDING CODES

Pursuant to Sections 39-4109 and 39-4109A, Idaho Code, the Board adopts the following international codes with identified amendments:

01.International Building Code. The 2018 Edition, including appendices pertaining to building accessibility, with the following amendments:
a. Delete Section 305.2.3 and replace with the following: 305.2.3 Twelve (12) or fewer children in a dwelling unit. A facility such as the above within a dwelling unit and having twelve (12) or fewer children receiving such day care shall be classified as a Group R-3 occupancy or shall comply with the International Residential Code.
i. Delete Section 308.2.4 and replace with the following: 308.2.4 Five (5) or fewer persons receiving custodial care. A facility with five (5) or fewer persons receiving custodial care shall be classified as a Group R-3 occupancy or shall comply with the International Residential Code.
ii. Delete Section 308.3.2 and replace with the following: 308.3.2 Five (5) or fewer persons receiving medical care. A facility with five (5) or fewer persons receiving medical care shall be classified as a Group R-3 occupancy.
iii. Delete Section 308.5.4 and replace with the following: 308.5.4 Persons receiving care in a dwelling unit. A facility such as the above within a dwelling unit and having twelve (12) or fewer children receiving day care or having five (5) or fewer persons receiving custodial care shall be classified as a Group R-3 occupancy or shall comply with the International Residential Code.
b. Section 310.4: Add the following: "Dwelling units providing day care for twelve (12) or fewer children".
c. Section 310.4.1. Delete and replace with the following: 310.4.1 Care facilities within a dwelling. Care facilities for twelve (12) or fewer children receiving day care or for five (5) or fewer persons receiving personal care or custodial care that are within a one- or two-family dwelling are permitted to comply with the International Residential Code.
d. Add new Section 602.1.2: 602.1.2 Alternative provisions. As an alternative to the construction types defined in Sections 602.2 through 602.5, buildings and structures erected or to be erected, altered, or extended in height or area may be classified as construction type IV-A, IV-B, or IV-C in accordance with the provisions adopted in Paragraph 004.01.b of these rules. Buildings and structures classified as construction type IV-A, IV-B, or IV-C shall comply with the provisions adopted in Paragraph 004.01.h of these rules and all other applicable provisions of this code.
e. Table 2902.1 Minimum Number of Required Plumbing Fixtures. Delete footnotee and replace with the following: e For business occupancies, excluding restaurants, and mercantile occupancies with an occupant load of thirty (30) or fewer, service sinks shall not be required.
f. Table 2902.1 Minimum Number of Required Plumbing Fixtures. Delete footnote f and replace with the following: f Drinking fountains are not required for an occupant load of thirty (30) or fewer.
g. Section 3113 Relocatable Buildings. Delete.
02.International Building Code, 2021 Edition. The following provisions of the 2021 Edition related to mass timber construction:
a. In Section 202, the definitions of the terms MASS TIMBER; NONCOMBUSTIBLE PROTECTION (FOR MASS TIMBER); SECONDARY STRUCTURAL MEMBERS; and WALL, LOAD BEARING;
b. Sections 403.3.2, 508.4.4.1, 509.4.1.1, 602.4 through 602.4.3.6, 703.6, 703.7, 704.4, 722.7 through 722.7.2.2, 1705.5.3, 1705.20, 2304.10.1, 3313.1 through 3313.3.3, 3313.5, and 3314.1;
c. Tables 504.3, 504.4, 506.2, 601, 705.5, 722.7.1(1), 722.7.1(2), and 1705.5.3, including any note following each table adopted in this subparagraph; and
d. In Chapter 35, the referenced standards ANSI/APA PRG 320-2019: Standard for Performance-rated Cross-laminated Timber, referenced in Sections 602.4 and 2303.1.4, and ASTM D3498-03(2011): Standard Specification for Adhesives for Field-Gluing Plywood to Lumber Framing for Floor Systems, referenced in Section 703.7.
03.International Residential Code, 2018 Edition. Parts I, II, III, and IX of the 2018 Edition for one (1)- and two (2)- family dwellings, with the following amendments:
a. Section R101.2 Scope. Delete the exception and replace with the following: Exception: The following shall also be permitted to be constructed in accordance with this code:
1. Owner-occupied lodging houses with five (5) or fewer guestrooms and ten (10) or fewer total occupants.
2. A care facility with five (5) or fewer persons receiving custodial care within a dwelling unit or single-family dwelling.
3. A care facility for five (5) or fewer persons receiving personal care that are within a dwelling unit or single-family dwelling.
4. A care facility with twelve (12) or fewer children receiving day care within a dwelling unit or single-family dwelling.
b. Section R105.2. Amend Item number 7 under the "Building" subheading Replace the words "24 inches (610 mm)" with "four (4) feet (1219) mm)"
c. Section R105.2. Add the following exemption under the "Building" subheading: 11. Flag poles.
d. Section R301.2.1.2 Protection of Openings. Delete.
e. Table R302.1(1). Delete and replace with the following:

TABLE R302.1(1) - EXTERIOR WALLS

EXTERIOR WALL ELEMENT

MINIMUM FIRE-RESISTANCE RATING

MINIMUM FIRE SEPARATION DISTANCE

Walls

Fire-resistance rated

1 hour-tested in accordance with ASTM E 119, UL263, or Section 703.3 of the International Building Code with exposure from both sides

< 3 feet

Not fire-resistance rated

0 hours

> 3 feet

Projections

Fire-resistance rated

1 hour on the underside, or heavy timber, or fire retardant-treated wooda,b

[GREATER THAN EQUAL TO] 2 feet to < 3 feet

Not fire-resistance rated

0 hours

[GREATER THAN EQUAL TO] 3 feet

Openings in Walls

Not allowed

N/A

< 3 feet

25% maximum of wall area

0 hours

[GREATER THAN EQUAL TO] 3 feet to < 5 feet

Unlimited

0 hours

5 feet

Penetrations

All

Comply with Section R302.4

< 3 feet

None required

[GREATER THAN EQUAL TO] 3 feet

For SI: 1 foot = 304.8 mm.

N/A = Not Applicable

aThe fire-resistance rating shall be permitted to be reduced to zero (0) hours on the underside of the eave overhangif fireblocking is provided from the wall top plate to the underside of the roof sheathing.

"The fire-resistance rating shall be permitted to be reduced to zero (0) hours on the underside of the rake overhang where gable vent openings are not installed.

f. Delete Table R302.6 Dwelling-Garage Separation and replace with the following table:

Separation

Material

From the residence, attics, and habitable rooms above the garage

Not less than 5/8-inch Type X gypsum board or

Structure(s) supporting floor/ceiling assemblies used for separation required by this section

equivalent applied to the garage side

Garages located less than 3 feet from a dwelling unit on the same lot

Not less than 5/8-inch Type X gypsum board or equivalent applied to the interior side of exterior walls that are within this area

g. Section R302.13 Fire protection of floors. Delete.
h. Section R303.4. Delete and replace with the following: Mechanical Ventilation. Dwelling units shall be provided with whole-house mechanical ventilation in accordance with Section M1505.4.
i. Section R313.1 Townhouse automatic fire sprinkler systems. Delete the exception and replace with the following: Exception: Automatic residential fire sprinkler systems shall not be required in townhouses where either two (2) one (1)-hour fire-resistance-rated walls or a common two (2)-hour fire-resistance rated wall, as specified in item number 2 of Section R302.2.2 is installed between dwelling units or when additions or alterations are made to existing townhouses that do not have an automatic residential fire sprinkler system installed.
j. Section R313.2 One- and two-family dwellings automatic fire sprinkler systems. Delete.
k. Section R314.2.2 Alterations, repairs and additions Exception Item #2. Delete.
l. Section R315.2.2 Alterations, repairs and additions Exception Item #2. Delete.
m. Section R322.1.10 As-built elevation documentation. Delete.
n. Tables R403 Minimum Depth (D) and Width (W) of Crushed Stone Footings (inches), R403.1(1) Minimum Width and Thickness for Concrete Footings for Light-Frame Construction (inches), R403.1(2) Minimum Width and Thickness for Concrete Footings for Light-Frame Construction and Brick Veneer (inches), and R403.1(3) Minimum Width and Thickness for Concrete Footings with Cast-In-Place or Fully Grouted Masonry Wall Construction (inches). Delete.
o. Add the following as Table R403.1:

TABLE R403.1

MINIMUM WIDTH OF CONCRETE, PRECAST, OR MASONRY FOOTINGS (inches)a

LOAD-BEARING VALUE OF SOIL (psf)

1,500

2,000

3,000

[GREATER THAN EQUAL TO] 4,000

Conventional light-frame construction

1-Story

12

12

12

12

2-Story

15

12

12

12

3-Story

23

17

12

12

4-inch brick veneer over light frame or 8-inch hollow concrete masonry

1-Story

12

12

12

12

2-Story

21

16

12

12

3-Story

32

24

16

12

8-inch solid or fully grouted masonry

1-Story

16

12

12

12

2-Story

29

21

14

12

3-Story

42

32

21

16

For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kPa.

aWhere minimum footing width is twelve (12) inches, use of a single wythe of solid or fully grouted twelve (12)-inch nominal concrete masonry units is permitted.

p. Section R403.1.1. Delete and replace with the following: R403.1.1 Minimum size. Minimum sizes for concrete and masonry footings shall be as set forth in Table R403.1 and Figure R403.1(1). The footing width (W) shall be based on the load bearing value of the soil in accordance with Table R401.4.1. Spread footings shall be at least six (6) inches in thickness (T). Footing projections (P) shall be at least two (2) inches and shall not exceed the thickness of the footing. The size of footings supporting piers and columns shall be based on the tributary load and allowable soil pressure in accordance with Table R401.4.1. Footings for wood foundations shall be in accordance with the details set forth in Section R403.2 and Figures R403.1(2) and R403.1(3).
q. Section R602.10. Delete and replace with the following: Buildings shall be braced in accordance with this Section or, when applicable Section R602.12, or the most current edition of APA System Report SR-102 as an alternate method. Where a building, or portion thereof, does not comply with one (1) or more of the bracing requirements in this Section, those portions shall be designed and constructed in accordance with Section R301.1.
04.International Existing Building Code. 2018 Edition.
05.International Energy Conservation Code - Commercial Provisions. The 2018 Edition with the following amendments:
a. Add new Section C101.5.2: C101.5.2 Industrial, electronic, and manufacturing equipment. Buildings or portions thereof that are heated or cooled exclusively to maintain the required operating temperature of industrial, electronic, or manufacturing equipment shall be exempt from the provisions of this code. Such buildings or portions thereof shall be separated from connected conditioned space by building thermal envelope assemblies complying with this code.
b. Add the following Exemptions to section C402.1.1:
i. Exemption 4. Accessory utility and storage buildings and sports practice buildings accessory to A, B, and E occupancies where buildings maintain no heating or cooling or where intermittent heating and cooling systems are installed.
ii. Exemption 5. Buildings for domestic water wells, irrigation wells, sewer pump facilities, and sewer lift station buildings where equipment produces internal heat loads and where intermittent heating or cooling is provided to prevent freezing or overheating of equipment.
c. Add the following as exception number 7 under Section C403.5 Economizers (Prescriptive): 7. Unusual outdoor air contaminate conditions - Systems where special outside air filtration and treatment for the reduction and treatment of unusual outdoor contaminants, makes an air economizer infeasible.
06.International Energy Conservation Code - Residential Provisions. The 2018 Edition with the following amendments:
a. R202 General Definitions. Add the following to the definition of "Conditioned Space": This definition shall not apply to garage spaces or other similar spaces where heating or cooling is installed for frost protection or intermittent use.
b. Table R402.1.2 Insulation and Fenestration Requirements by Component. Delete the rows in climate zones "5 and Marine 4" and "6" and replace with the following:

TABLE R402.1.2

INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENTa

Climate Zone

Fenestration U- Factorb

SkylightbU-factor

Glazed Fenestration SHGCb,e

Ceiling R-Value

Wood Frame Wall R-Value

Mass Wall R-Valuei

Floor R-Value

Basementc Wall R-Value

Slabd R-Value & Depth

Crawlspacec Wall R-Value

5

0.32

0.55

NR

38

20 or 13+5h

13/17

30g

15/19

10, 2 ft

15/19

6

0.30

0.55

NR

49

22 or 13+5h

15/20

30g

15/19

10, 4 ft

15/19

c. Table R402.1.2 - Insulation and Fenestration Requirements by Component. Add the following as footnote k to the Table title: k. For residential log home building thermal envelope construction requirements see Section R402.6.
d. Table R402.1.4 Equivalent U-Factors. Delete the rows in climate zones "5 and Marine 4" and "6" and replace with the following:

TABLE R402.1.4

EQUIVALENT U-FACTORSa

Climate Zone

Fenestration U-factor

Skylight U-factor

Ceiling U-factor

Frame Wall U-factor

Mass Wall U-factorb

Floor U-factor

Basement Wall U-factor

Crawlspace Wall U-factor

5

0.32

0.55

0.030

0.060

0.082

0.033

0.050

0.055

6

0.30

0.55

0.026

0.057

0.060

0.033

0.050

0.055

e. Section R402.4.1.2. Add the following exception: Visual Inspection. The Permit Holder will determine at the time of permit application the method of determining building envelope tightness. A visual inspection shall be considered acceptable in lieu of testing when the items listed in Table R402.4.1.1, applicable to the method of construction, are field verified.
f. Add new Section R402.6: R402.6 Residential log home thermal envelope. Residential log home construction shall comply with Section R401 (General), Section R402.4 (Air leakage), Section R402.5 (Maximum fenestration U-factor and SHGC), Section R403.1 (Controls), the mandatory sections of Sections R403.3 through R403.9, Section R404 (Electrical Power and Lighting Systems), and either 1., 2., or 3. as follows:
1. Sections R402.2 through R402.3, Section R403.3.1 (Insulation), Section R404.1 (Lightning equipment), and Table R402.6 (Log Home Prescriptive Thermal Envelope Requirements by Component).
2. Section R405 (Simulated Performance Alternative).
3. REScheck (U.S. Department of Energy Building Codes Program).
g. Add new Table R402.6:

TABLE R402.6

LOG HOME PRESCRIPTIVE THERMAL ENVELOPE REQUIREMENTS BY COMPONENT

For SI: 1 foot = 304.8 mm.

Climate Zone

Fenestration U-factora

Skylight U-factor

Glazed Fenestration SHGC

Ceiling R-value

Min. Average Log Size In Inches

Floor R-value

Basement Wall R-valued

Slab R-value & Depthb

Crawl Space Wall R-valued

5, 6 - High efficiency equipment pathc

0.32

0.60

NR

49

5

30

15/19

10, 4 ft.

10/13

aThe fenestration U-factor column excludes skylights. The SHGC column applies to all glazed fenestration.

bR-5 shall be added to the required slab edge R-values for heated slabs.

c90% AFUE natural gas or propane, 84% AFUE oil, or 15 SEER heat pump heating equipment (zonal electric resistance heating equipment such as electric base board electric resistance heating equipment as the sole source for heating is con-sidered compliant with the high efficiency equipment path).

d"15/19" means R-15 continuous insulated sheathing on the interior or exterior of the home or R-19 cavity insulation at the interior of the basement wall. "15/19" shall be permitted to be met with R-13 cavity insulation on the interior of the basement wall plus R-5 continuous insulated sheathing on the interior or exterior of the home. "10/13" means R-10 continuous insulated sheathing on the interior or exterior of the home or R-13 cavity insulation at the interior of the basement wall.

5

0.32

0.60

NR

49

8

30

10/13

10, 2 ft.

10/13

6

0.30

0.60

NR

49

8

30

15/19

10, 4 ft.

10/13

aThe fenestration U-factor column excludes skylights. The SHGC column applies to all glazed fenestration.

bR-5 shall be added to the required slab edge R-values for heated slabs.

c90% AFUE natural gas or propane, 84% AFUE oil, or 15 SEER heat pump heating equipment (zonal electric resistance heating equipment such as electric base board electric resistance heating equipment as the sole source for heating is considered compliant with the high efficiency equipment path).

d"15/19" means R-15 continuous insulated sheathing on the interior or exterior of the home or R-19 cavity insulation at the interior of the basement wall. "15/19" shall be permitted to be met with R-13 cavity insulation on the interior of the basement wall plus R-5 continuous insulated sheathing on the interior or exterior of the home. "10/13" means R-10 continuous insulated sheathing on the interior or exterior of the home or R-13 cavity insulation at the interior of the basement wall.

Idaho Admin. Code r. 24.39.30.600