Section 6-77-34 - Temperature derating factor (T) for steel pipe

The temperature derating factor to be used in the design formula in section 6-77-29 is determined as follows:

Gas temperature in degrees Fahrenheit | Temperature derating factor (T)
250 or less.............................................| 1.000
300................................................| 0.967
350................................................| 0.933
400................................................| 0.900
450................................................| 0.867

For intermediate gas temperatures, the derating factor is determined by interpolation.